Notifier NFC-50/100 is the First Command multipurpose emergency voice evacuation panel for fire, mass notification or both, 120 VAC version. It comes with one speaker circuit, a built-in 50 W, 25 V amplifier, an integral microphone, field-configurable tone generators and fourteen field-programmable messages of up to 60 seconds each.
Specifications
| Audio power |
50 W standard; 100 W with a second NFC-BDA-25/70V amplifier |
| Speaker circuits |
1 standard, 2 with the secondary amplifier, up to 8 with the NFC-CE6 |
| Speaker voltage |
25 V; 70 V with NFC-XRM-70V or NFC-BDA-25/70V |
| Messages |
14 field programmable, up to 60 seconds each |
| NAC |
One Class B or Class A, 2.0 A synchronized, 24 VDC |
| Relays |
Three Form-C: AC power, trouble, MNS active |
| Auxiliary power |
500 mA at 24 VDC special application |
| Primary power |
120 VAC, 60 Hz, 3.5 A |
| Battery charger |
Lead-acid, 27.3 V float, up to 26 AH (cabinet holds 18 AH), 12 AH minimum |
Features
- Works as an adjunct to any certified FACP through reverse polarity or contact closure, or stand-alone for non-fire use
- Direct serial activation from the NFW-100X, NFW2-100, NFS-320 or NFS2-640
- Eight command input circuits; CMD 1 and CMD 2 can follow an FACP NAC reverse polarity
- Night ring activation from a building PBX
- Programmed from a laptop with the built-in programming utility
- Up to eight remote consoles such as the NFC-LOC, NFC-RPU and NFC-RM
Related models
NFC-50/100E is the 240 VAC, 50 Hz version. Options include the NFC-BDA-25/70V backup or second amplifier, the NFC-CE6 circuit expander and the NFC-XRM-70V transformer module.
Documents
FAQ
How many speaker zones does the NFC-50/100 support?
One speaker circuit as standard. A second amplifier (NFC-BDA-25/70V) gives two, and the NFC-CE6 module expands the system to eight speaker circuits.
Can it run 70 V speakers?
Yes, by adding the NFC-XRM-70V transformer module or an NFC-BDA-25/70V secondary amplifier. The standard output is 25 V.
How is it activated by a fire alarm panel?
By reverse polarity or contact closure from any certified FACP, or by direct serial link from the NFW-100X, NFW2-100, NFS-320 or NFS2-640.
What batteries does it need?
Lead-acid batteries of 12 AH minimum. The charger supports up to 26 AH, and the cabinet holds up to 18 AH.