Notifier NDM-100 — dual monitor module for Notifier FireWarden Series intelligent addressable fire alarm control panels.
The NDM-100 provides two independent two-wire initiating device circuits (IDCs) at two separate, consecutive addresses. It monitors normally open contact fire alarm and supervisory devices, such as conventional heat detectors, pull stations and flow or tamper switches, and has a single panel-controlled LED.
Specifications
| Circuits |
Two Class B (Style B) IDCs; Class A is not supported |
| Operating voltage |
15 to 32 VDC |
| Current |
750 µA average (LED flashing), 6.4 mA maximum (LED on) |
| Maximum IDC wiring resistance |
1,500 ohms |
| EOL resistor |
47K ohms |
| Temperature |
32°F to 120°F (0°C to 49°C), 10% to 93% RH non-condensing |
| Dimensions |
4.5 in. H x 4 in. W x 1.25 in. D |
| Mounting |
4 in. square x 2-1/8 in. deep box, or SMB500 surface-mount box |
Installation notes
- The module assigns itself two addresses starting with the one set; for example, set to 26 it uses 26 and 27.
- The "ones" address can only be 0, 2, 4, 6 or 8. Terminals 6 and 7 use the first address, terminals 8 and 9 the second.
- An "A" suffix (NDM-100A) marks the ULC version for Canada.
Related models
-
NMM-100 — standard monitor module, Class A or Class B.
-
NMM-100P — miniature monitor module.
-
NZM-100 — zone module for two-wire smoke detectors.
Documents
FAQ
Can the NDM-100 be wired Class A?
No. It provides two Class B (Style B) circuits only; Class A is not supported in any application. Use the NMM-100 for a Class A input.
How many addresses does it use?
Two consecutive addresses. The ones digit of the set address must be 0, 2, 4, 6 or 8.
Which panels is it for?
Notifier FireWarden Series intelligent addressable control panels.
What end-of-line resistor does it need?
A 47K ohm EOL resistor on each circuit, with up to 1,500 ohms of IDC wiring resistance.