Notifier NBG-12 — dual-action, non-coded conventional manual fire alarm pull station with an SPST normally open switch, screw terminal connections and a hex lock.
The NBG-12 provides an alarm initiating input to conventional fire alarm control panels and monitor modules. Pushing in and then pulling down the handle operates the alarm switch; the handle latches down and the word ACTIVATED appears in bright yellow. To reset, a quarter turn of the hex key opens the cover, the spring-loaded handle returns, and closing the cover resets the switch. The station can be opened for inspection without initiating an alarm.
Specifications
| Model |
NBG-12 |
| Action |
Dual action (push in, pull down) |
| Switch |
SPST normally open, gold plated |
| Contact rating |
0.25 A at 30 VAC or VDC |
| Lock |
Hex lock (17007 hex key included) |
| Wiring |
Four-position terminal strip, up to 12 AWG |
| Dimensions |
5.5 in. H x 4.121 in. W x 1.39 in. D |
| Construction |
Polycarbonate cover, backplate and handle |
| Certifications |
C(UL)US S692, CSFM 7150-0028:199, FM, MEA 67-02-E |
Installation notes
- Surface mount with the SB-10 metal or SB-I/O plastic backbox
- Semi-flush mount to a single-gang, double-gang or 4 in. square electrical box; BG12TR trim ring optional
- Meets ADA 5 lb maximum pull force and UL 38
- Designed to replace the legacy NBG-10 Series
Related models
- NBG-12L: same station with key lock
- NBG-12S: single-action version with pigtail leads
- NBG-12LOB: key-lock version with outdoor backbox
- NBG-12LX: addressable version
Documents
FAQ
Is the NBG-12 key or hex reset?
The NBG-12 uses a hex lock and ships with the 17007 9/64 in. hex key. The NBG-12L is the key-lock version.
Can it be mounted on the surface?
Yes, on the SB-10 metal or SB-I/O plastic surface backbox. It also semi-flush mounts to a single-gang, double-gang or 4 in. square box.
Is it addressable?
No. The NBG-12 is a conventional station with a normally open switch for an initiating device circuit or monitor module. The NBG-12LX is the addressable model.
What does it replace?
The NBG-12 Series was designed to replace the legacy NBG-10 Series.