Notifier FST-951R — white, low-profile intelligent rate-of-rise thermal sensor for Notifier addressable systems, FlashScan protocol only.
The FST-951 Series plugs into a separate base on a two-wire SLC loop and uses one panel address, set with rotary decimal switches. Each detector reports its type and status when polled, blinks its LEDs when polled, and can be tested from the panel or locally with a magnet. The FST-951R responds to a rate of rise of 15°F (8.3°C) per minute. The FST-951 Series is the direct replacement for the FST-851 Series.
Specifications
| Model |
FST-951R |
| Type |
Intelligent rate-of-rise thermal sensor |
| Protocol |
FlashScan only |
| Rate of rise |
15°F (8.3°C) per minute |
| Color |
White |
| Voltage range |
15–32 VDC peak |
| Standby current |
200 µA at 24 VDC (max. avg.) |
| Alarm current |
4.5 mA at 24 VDC |
| Spacing |
UL 50 ft center-to-center; FM 25 x 25 ft |
| Operating temperature |
-4°F to 100°F (-20°C to 38°C) |
| Humidity |
10–93% RH, non-condensing |
| Height |
2.0 in.; diameter set by base (6.1 in. on B300-6, 4 in. on B501) |
| Certifications |
UL/ULC S747, FM approved, CSFM 7270-0028:0502 |
Installation notes
- Mount the base on an electrical backbox at least 1.5 in. deep
- End-of-line resistors are not required on the SLC; T-taps are permitted for Class B (Style 4) wiring only
- Optional RA100Z remote LED annunciator connects to the remote LED output
- When using relay or sounder bases, check the ISO-X installation sheet for limits between isolators
Related models
- FST-951R-IV: ivory rate-of-rise version, FlashScan and CLIP
- FST-951: 135°F fixed thermal sensor
- FST-951H: 190°F high-temperature thermal sensor
- FST-951RA: version with ULC certification
FAQ
Will the FST-951R work on a CLIP loop?
No. The white FST-951R is FlashScan only. The ivory FST-951R-IV supports both FlashScan and CLIP.
Does it replace the FST-851R?
Yes. Notifier designed the FST-951 Series as the direct replacement for the FST-851 Series.
Which bases can it use?
It plugs into the B300-6 6 in. flanged base or the B501 4 in. base, as well as relay, isolator and sounder bases such as the B224RB, B224BI and B200S.
What spacing is allowed?