Notifier DS-AMP is the 120 VAC Digital Series amplifier used with the DS-DB distribution board to add bulk audio amplification to a Notifier Digital Voice Command (DVC) system. It delivers 125 W at 25 VRMS, or 100 W at 70 VRMS with the DS-XF70V step-up transformer. Up to four DS-AMP amplifiers can be connected to one DS-DB.
Specifications
| Part number |
DS-AMP (120 VAC, 50/60 Hz) |
| Audio power |
125 W at 25 VRMS; 100 W at 70 VRMS (requires DS-XF70V) |
| AC input current (TB4) |
4.1 A maximum for 25 V (125 W); 3.55 A maximum for 70 V (100 W) |
| AC wiring |
12-14 AWG with 600 VAC insulation |
| High-level output (TB3) |
Non-power-limited, supervised by the DS-DB; 14-18 AWG twisted pair, unshielded |
| Audio in (TB2) |
Power-limited, supervised by the DS-DB; 14-18 AWG twisted pair, unshielded |
| Communication |
EIA-485 with the DS-DB |
| Battery connection |
Supplied cables; for battery sharing use 12 AWG in the same cabinet or in conduit up to 20 ft (6.09 m) |
| Weight |
6.7 lb (3.04 kg) |
| Listings |
UL and ULC listed S635; CSFM 7165-0028:0243 (NFS2-640/NFS-320), 7165-0028:0224 (NFS2-3030); FDNY COA #6121, #6114 |
Compatibility and installation notes
- Ships already installed on its chassis; mounts in one row of any EQ or CAB-4 Series cabinet. A DP-1B dress panel (ordered separately) can cover the CAB-4 row.
- The DS-XF70V step-up transformer mounts on the front of the amplifier for 70 VRMS operation and is ordered separately.
- Backup audio: add a DS-BDA or a dedicated DS-AMP. A DS-BDA backing up a 70 VRMS DS-AMP also needs a DS-XF70V.
Related models
-
Notifier DS-DB Digital Series distribution board
- DS-AMPE, 220-240 VAC version
- DS-BDA backup amplifier; DS-XF70V step-up transformer
Documents