Kidde WG4RF-HVMHC — Genesis WG4 outdoor-rated horn strobe, red housing, FIRE marking, selectable high-candela strobe.
One low-profile appliance serves wet and harsh locations such as parking garages and process areas as well as ordinary indoor space. A switch picks one of four candela steps and stays readable through a sealed viewport after the cover closes; cutting jumpers selects coded horn operation, low horn volume or temporal strobe flash.
- UL 1971 indoor strobe: 102, 123, 147 and 161 cd at positions D, C, B and A
- UL 1638 outdoor at -35 °C: 41, 50, 60 and 65 cd
- 24 VDC current at those positions: 240, 271, 327 and 365 mA
- Horn 90.5 dBA temporal high at 24 V per UL 464; tone 3.2 kHz
- -40 to 151 °F; 5.6 × 8.5 × 1.4 in.; wiring 12 to 18 AWG
The near-miss is WG4RF-HVMC, the same red FIRE-marked housing with the standard-candela strobe of 15, 29, 70 and 87 cd; WG4RF-H is horn only. WG4WF-HVMHC is white, WG4RN-HVMHC unmarked. Outdoor surface mounting needs a Model 449 or 74347U box; skirts WG4RTS and WG4WTS and gasket WG4GSKT are separate.