| Air Velocity Range |
300 to 4000 ft/min. (1.5 to 20.3 m/sec) |
| Operating Environment Temperature |
32 - 100º F (0 to 38º C) Humidity: 0 to 93% RH, non-condensing |
| Storage Environment Temperature |
-4 to 140º F (-20 to 60º C); Humidity: 0 to 93% RH, non-condensing |
| ULI/ULC Sensitivity Range |
0.5% to 4.36% obscuration/foot (for Optica) |
| Dimensions |
7-3/8 inches (188mm) W x 7 inches (178mm) H x 5 inches (127mm) D |
| Material and Finish |
18 Gauge Galvanized Steel, Red - Baked Enamel |
| Conduit Knockouts |
4, Combination 1/2 inch & 3/4 inch |
| Operating Voltage |
15.2 to 19.95 Vdc (19 Vdc nominal) |
| Temperature |
32 to 120ºF (0 to 49ºC) |
| Onboard LED Operation |
Red LED - flashes when in alarm or test state |
| Mounting North American electric box |
2 inch deep 2-gang or 4 inch square ; European electric box: 100 mm square |