| Controller |
6.75” x 5.45” x 1.90” inches (17.15 cm x 13.84 cm x 4.83 cm) |
| Sensor |
8.70” x 5.45” x 1.90” (22.10 cm x 13.84 cm x 4.83 cm) |
| Controller with sensor |
14.51” x 5.45” x 1.90” (36.86 cm x 13.84 cm x 4.83 cm) |
| Wire size High voltage power input terminals |
(L&N): #12 to #22 AWG All others: #14 to #22 AWG |
| Test Station to Controller |
10 ohms max. per wire (i.e. 621 feet with 22 AWG, 3,952 feet with 14 AWG) |
| Controller Interconnect |
5 ohms max between first and last controller (i.e. 310 feet with 22 AWG, 1,976 feet with 14 AWG) |
| Air velocity rating |
100 to 4,000 ft/min and meets the required minimum air pressure differential |
| Air pressure differential |
0.005 to 1.00 inches of water |
| Sensitivity |
0.67 to 2.46 %obscuration/ft |
| Reset time |
2 seconds, max. |
| Power up time |
8 seconds, max. |
| Alarm test response time |
5 to 7 seconds |
| Alarm initiation relay Quantity |
1 Style: Normally open Ratings: 2.0 A at 30 Vdc (resistive) |
| Style |
Form C |