Kidde K-278B-1110 — 278B series non-coded double action fire alarm station, screw terminals, tool reset.
Raising an alarm takes two deliberate actions: the upper door marked LIFT THEN PULL HANDLE must be lifted before the handle marked PULL FOR FIRE can be pulled. Pulling it breaks a glass rod and throws a toggle switch, and the handle latches until the station is opened with a tool. The rod is then replaced.
- Single pole general alarm contact wired open circuit; no presignal keyswitch
- Contacts rated 3.0 A at 30 VAC and 1.0 A at 28 VDC, resistive
- Red Lexan 940 housing with white raised letters; 1 lb (0.4 kg)
- Semi-flush to a 4 in. square box with a single gang plaster cover 2-1/4 in. deep, or surface to a 276B-RSB box
- UL certified; the ULC certification in the table belongs to K-278B-1120
- 276-GLR supplies replacement glass rods; the optional 276-R kit adds a 560 Ω resistor
K-278B-1120 is the same station with key reset and a ULC certification, K-278B-1320 uses a double pole contact, K-278B-1420 adds a closed circuit contact and K-278B-2320 adds presignal. The K-279B numbers use wire leads.