Kidde Fenwal 85-100000-100 — Control Head Monitor with explosion proof assembly, a supervisory switch reporting the position of a control head on a suppression discharge valve.
It is fitted between the discharge valve and an electric or electric/cable operated control head, so an existing system gains supervision without either part being replaced, and the explosion proof housing serves normal and classified areas alike.
- Body and trigger brass; weight 1.7 lbs.
- Two wire pairs, blue and white, from a 1/2-14 NPT entry
- Contacts open in the activated position, with an end of line resistor after the last device; Ta -40 to 60 °C
- Approval varies by system: UL, ULC and FM on ECS-500, ECS 360 and ADS, UL only on the two FE-13 systems, FM only on the Natura inert gas system
- Marked Class I Div 1 Groups C and D, Zone 1 AEx d IIB T6, Class II and III Div 1 Groups E, F and G
- Conduits sealed within 18 in. of the component in US and Canadian installations
Order spacer 85-100000-002 as well if the monitor goes onto the stackable pressure operated control head 82-878750-000, where Kidde states it is required.