Kidde 84-900001-001 — AEGIS-PHX conventional fire alarm suppression control unit assembly in a red NEMA 1 enclosure, 120/240 VAC, with seven initiating circuits, five releasing/notification circuits and four relays.
The AEGIS-PHX controls Kidde Fire Systems suppression systems, including ECS-500 and ADS clean agent, Natura inert gas, high and low pressure CO2, WHDR wet chemical and IND dry chemical, as well as sprinkler supervisory, deluge/pre-action, foam and water mist systems by others. It can retrofit existing AEGIS, AEGIS 2.0 and AEGIS-XLT installations without replacing the back box.
Specifications
| Part number |
84-900001-001 (AEGIS-PHX control unit assembly) |
| Initiating circuits |
Seven, Class A or Class B |
| Releasing/notification circuits |
Five, Class A or Class B |
| Relays |
Three programmable and one trouble, Form C |
| Other outputs |
Two open collector outputs; two 24 VDC regulated auxiliary outputs |
| AC input |
120/240 V, 50/60 Hz, switch selected |
| Power supply |
5.4 A, filtered and regulated |
| Battery charging |
Up to 70 Ah; space for two 12 V 12 Ah batteries |
| Display |
4-line, 40-character LCD |
| Enclosure |
NEMA 1 with door closed, key lock, semi-flush option |
| Weight |
18 lb (standard unit) |
Installation notes
- In-line releasing device: 06-220023-001 for Class B circuits, or 76-800000-004 for Class A
- 15 pre-defined configurations selectable at the unit or in the remote configuration utility
- Ethernet connection for remote computer use; optional large capacity battery enclosure 76-100010-001
Related models
- 84-900001-002: same unit with door-mounted manual release, abort and key maintenance bypass switch kits
- 84-900732-001: AEGIS-PHX retrofit kit with PCB and solid door
Documents
FAQ
Which suppression systems can the AEGIS-PHX control?
Kidde ECS-500 and ADS clean agent, Natura inert gas, HP and LP CO2, WHDR wet chemical and IND dry chemical systems, plus sprinkler supervisory, deluge/pre-action, foam and water mist systems by others.
What is the difference between -001 and -002?
The 84-900001-002 adds door-mounted manual release, abort and key maintenance bypass switch kits. The 84-900001-001 is the standard assembly.
Which in-line releasing device is needed?
P/N 06-220023-001 for a Class B releasing circuit, or 76-800000-004 for Class A.
Can it replace an older AEGIS panel?
Yes. It fits existing AEGIS, AEGIS 2.0 and AEGIS-XLT enclosures, needing only PCB and door replacement.