Honeywell Home 5193SD is a V-Plex addressable photoelectric smoke detector designed for open area protection. It is used with compatible UL or ULC certified Honeywell Home control panels that support V-Plex technology; the manufacturer's product page names VISTA control panels with V-Plex polling loops.
The detector has an optical sensing chamber and an advanced microprocessor. Built-in drift compensation algorithms automatically maintain proper operation at factory calibrated detection levels, even when sensitivity changes because contaminants settle in the chamber. Photoelectric detectors like the 5193SD are suited to slow, smoldering fires.
Features
- The mounting base can be pre-wired to the system, which simplifies installation
- Included hardware and large mounting ports accept drywall anchors for easy surface mounting
- Two LEDs (green and red) give local indication of normal operation, alarm, out of sensitivity and trouble conditions
- Test button for periodic testing of detector circuitry and to verify the detector is within sensitivity limits
- Built-in tamper switch tells the control panel if the detector is removed from its base
- Tamper-resistant element prevents removal from the base without tools
Specifications
| Model |
5193SD |
| Technology |
V-Plex addressable photoelectric smoke detection |
| Operating current |
LED on: 2.8 mA; LED off: 1.2 mA |
| Size |
5.3 in diameter, 2 in high; 6.3 oz (178.6 g) |
| Operating temperature |
32°F to 100°F (0°C to 38°C) |
| Operating humidity |
0% to 95%, non-condensing |
| Standard |
UL 268 certified |
Compatibility
Use the 5193SD only with control panels that support V-Plex addressable polling loop technology. Confirm the panel model before ordering.
Specifications are taken from the Honeywell Home (Resideo) product page for the 5193SD. Manufacturer specifications are subject to change without notice.