Gentex STRR — 120 VAC multi-criteria smoke alarm, catalog number 917-0072-002, with an integral 135°F rate of rise thermal and two sets of relay contacts.
The S Series is a self contained evacuation device for dwelling units, not a system detector on a signaling line circuit: it sounds its own horn, holds a 9V battery for back-up, and tandem interconnects with other Gentex alarms. The suffix names what this model adds, T for the integral thermal and RR for the second relay pair.
- Multi-criteria photoelectric light scattering sensing, nominal 2.5% obscuration
- 85 dBA evacuation piezo horn at 10 feet, 3100 Hz nominal
- Temporal 3 for smoke and heat; Temporal 4 when tandem interconnected with Gentex CO alarms
- Self restoring integral thermal, 135°F at 50 ft.
- Two Form A and two Form C auxiliary relay contacts rated 0.3 amps
- 120 VAC 60 Hz at 0.055 amps; ANSI/UL 217 9th Edition
The nearest sibling is SHRR (917-0073-002), which carries an isolated thermal instead of an integral one and whose wiring harness is not interchangeable. SR (917-0071-002) has a single Form A and Form C set and no thermal.
Documents
FAQ
What does the STRR add over the SR?
The STRR (917-0072-002) adds an integral 135°F rate-of-rise thermal and a second relay set: two Form A and two Form C contacts, versus one Form A and one Form C on the SR.
What battery does it use?
A 9V alkaline battery for back-up; Gentex specifies the Duracell MN1604 only.
Can it interconnect with other alarms?
Yes. The brown/yellow tandem wire interconnects it with S, SR, SHRR, H, C, CR, SC, SCR and SCRR models and the GN-503, CO1209 and S1209 series. It does not connect to legacy 7100/7103, 9120/9123 or GN-300 series alarms.
Is the wiring harness interchangeable?
No. Gentex states the STRR and SCRR harness is not interchangeable with other models, and the product will not work with the wrong harness.