Gentex SR (917-0071-002) is a 120 VAC single/multiple station smoke alarm with multi-criteria photoelectric sensing, 9V battery backup and one set of Form A/C auxiliary relay contacts. It replaces the Gentex S1209F and is used as an evacuation device in dwelling units such as apartments, hotels, dormitories and hospitals.
The relay lets the alarm signal other building equipment, and SR units can be tandem interconnected with other Gentex S Series smoke alarms and Gentex CO alarms so every unit sounds together.
Specifications
| Model |
SR, Gentex part number 917-0071-002 |
| Operating voltage |
120 VAC, 60 Hz |
| Operating current |
0.055 A at 120 VAC |
| Secondary power |
9V alkaline battery (Duracell MN1604) |
| Sensing |
Multi-criteria, photoelectric light scattering |
| Nominal sensitivity |
2.5% obscuration |
| Auxiliary relay |
1 Form A and 1 Form C, 0.5 A |
| Alarm horn |
85 dBA at 10 ft, Temporal 3 evacuation pattern, 3100 Hz nominal |
| Operating temperature |
40°F to 100°F |
| Size |
5.5" x 5.5" overall (5.0" x 5.0" at base), 1.75" deep |
| Certifications |
ANSI/UL 217 |
| Warranty |
One year from date of purchase |
Features
- Multi-criteria photoelectric smoke sensing
- Form A/C relay contacts with programmable relay operation
- Temporal 3 evacuation signal for smoke annunciation
- 16-hour alarm memory
- Push-button self test and functional test
- Quick-disconnect wire harness for 120 VAC and tandem interconnect
Related models
S (917-0070-002) without relay; STRR (917-0072-002) with thermal sensor and two relays; SHRR (917-0073-002) with isolated thermal and two relays; SCR and SCRR smoke/CO alarms with relay.
Documents
FAQ
Does the Gentex SR replace the S1209F?
Yes. The SR (917-0071-002) is the current Gentex model that replaces the S1209F single/multiple station smoke alarm with relay.
What are the relay contacts for?
The SR has one Form A and one Form C auxiliary relay contact rated 0.5 A, used to signal other equipment such as a monitor module or door holder.
Can it be interconnected?
Yes. Gentex S, SR, STRR, SHRR, SC, SCR and SCRR alarms can be tandem interconnected so all units sound together.
What battery does it use?
A 9V alkaline battery (Duracell MN1604) as secondary power, with 120 VAC as the primary supply.