Gamewell-FCI MS-7S — single action manual fire alarm pull station for conventional control panels.
The MS-7S is the single action, conventional member of the MS-7 Series. One pull operates a set of single pole contacts wired into an initiating device circuit, so it works with any UL certified conventional panel rather than reporting an address. Operating instructions and Braille text are moulded into the handle, and its tumbler lock is keyed alike with Gamewell-FCI panels.
- Connects by wire leads, not the screw terminals used on the double action MS-7
- Single pole contacts rated 0.25 amps at 30 VAC/VDC resistive
- Complies with the ADA 5 lb maximum pull force
- Lexan housing, 5 5/8 " H × 4 1/4 " W × 1 1/4 " D
- Surface or semi-flush on a double-gang or 4 in. square box
- Designed to comply with UL 864 9th Edition
The MS-7 is the double action conventional station and the MS-7SP adds Spanish text. MS-7AF and MS-7ASF are the Velociti addressable stations. Note the MS-7LR and MS-7LRA in the same family are agent release stations, not fire alarm stations. The outdoor certified station is the MS-7LOB.
Documents
FAQ
Is the MS-7S addressable?
No. It is a single action station for conventional fire alarm control panels, with single pole contacts and wire leads for an initiating circuit. The MS-7ASF is the addressable single action model.
Is it keyed like the panel?
Yes. All MS-7 Series stations include a key lock/reset keyed alike with Gamewell-FCI fire alarm control panels.
How is it mounted?
Surface or semi-flush on a standard double-gang or 4 in. square electrical box. The SB-I/O and SB-10 backboxes and BG12TR trim ring are available.
Does it meet ADA requirements?
Yes. MS-7 Series stations comply with the ADA 5 lb maximum pull force requirement.