Gamewell-FCI GWF402 is the Flex 402, a two-zone conventional fire alarm control panel for 120 VAC in a red cabinet. It suits small to medium-sized retail, office, multi-family and similar commercial or institutional buildings.
Its two initiating device circuits accept two- and four-wire smoke detectors, waterflow devices, pull stations, tamper switches and other normally open contact devices. The panel has one notification appliance circuit, Form-C alarm and trouble relays and 24 VDC resettable power for special applications, and it supervises wiring, AC voltage and battery level.
Specifications
| Zones |
2 IDCs, Class B (Style B) |
| NAC |
1, Class B (Style Y), 2.5 A total |
| AC power |
120 VAC, 50/60 Hz, 2.3 A |
| Battery charger |
27.6 VDC at 0.8 A, 18 Ah maximum; two 7 Ah batteries fit inside |
| Relays |
Form-C alarm and trouble, 2 A at 30 VAC |
| Resettable power |
24 VDC nominal, 500 mA |
| Backbox |
15.0 x 14.5 x 3.0 in. |
| Standard |
UL 864, 9th Edition |
Features
- ADA strobe synchronization and ANSI audible signals for NFPA 72
- Silence inhibit, auto-silence, selective silence and temporal or steady output
- Silent or audible walk test from the front keypad
- Zone disable and alarm verification selectable per zone
- Acknowledge, silence, alarm, walk test and reset controls
Related models
- GWF404: Flex 404, four-zone version with two NACs
- 4XTMF: transmitter module for municipal box or reverse polarity output, fits the Flex 402
- BB-17F: battery box for two batteries, 7 to 18 Ah
Documents
FAQ
How many zones and NACs does the GWF402 have?
Two Class B initiating device zones and one Class B notification appliance circuit rated 2.5 A total.
Can it be converted to Class A?
No. The CAC-4 Class A converter is for the Flex 404 only and cannot be used on the Flex 402.
What batteries does it take?
The charger supports up to 18 Ah. Two 7 Ah batteries fit inside the panel; larger sets go in a BB-17F battery box.
Which options fit the Flex 402?
The 4XTMF transmitter module mounts in the Flex 402. The XRM-24 transformer, 4XZMF relay module, 4XLMF annunciator driver and 411UD communicator are for the Flex 404 only.