The Gamewell-FCI Velociti® Series, addressable dual monitor module, AMM-2IF, features two Style B, Class B initiating device circuits, each with an end-of-line resistor
This module provides addresses for any device or group of devices connected to each circuit.
Any alarm-initiating devices with normally open (N.O.) dry contacts, such as heat detectors, 4-wire projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in these circuits.
The Velociti® Series uses a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls.
These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concentrates on the single device.
The net effect is response speed up to five times greater than earlier designs. The first circuit address is set via a rotary switch. The second circuit is automatically assigned the next higher address.
The module has a single panel-controlled red LED. The AMM-2IF module is designed for installation in the signaling line circuit of any Gamewell-FCI addressable control panel.
The AMM-2IF is designed to be mounted in a 4” square junction box, 2 1/8” deep. The initiating device circuit of the AMM-2IF can support a maximum line resistance of up to 40 ohms allowing the use of linear heat detection devices.
Ordering Information AMM-2IF: Monitor module, two circuits, Style B, Class B.