Edwards 3-ZA20A is a 20 W zoned audio amplifier for the EST3 life safety platform. The EST3 Audio Source Unit and live paging messages are multiplexed into eight separate digital audio channels, and each zoned amplifier has its own de-multiplexing circuitry, so any one of the eight channels can be placed on the amplifier's built-in speaker circuit. Channel selection is controlled by network software.
The speaker circuit is selectable for 25 or 70 VRMS and can be wired Class A or Class B. The amplifier also has a 3.5 A, 24 VDC power-limited notification appliance circuit, and an integral backup tone generator sounds a 1 kHz temporal (3-3-3) evacuation tone. It mounts in one local rail module (LRM) space in the same enclosures as other EST3 equipment and takes its power from the system power supplies through the rail.
Specifications
| Output power |
20 W |
| Output voltage |
25 VRMS or 70 VRMS, selectable |
| Audio wiring |
Class A or Class B, power limited; 15 kΩ EOL in Class B |
| NAC |
3.5 A, 24 VDC power limited, Class A or B |
| Frequency response |
400 Hz to 4 kHz, ±3 dB |
| Distortion |
Less than 7% THD |
| Backup tone |
1 kHz temporal (3-3-3) evacuation; 20 PPM alert |
| Current |
62 mA standby, 1120 mA alarm |
| Space |
1 LRM space |
| Environment |
32°F to 120°F (0°C to 49°C), 93% RH non-condensing |
Installation notes
- Field wiring connects to removable terminal strips
- Wire size 18 to 12 AWG (1.0 to 2.5 mm²)
- Supports up to 10 SIGA-CC1/2 modules
- Order a 3-FP filler plate when no LED or LED/switch module is installed on the operator layer
Related models
- 3-ZA40A: 40 W zoned amplifier, Class A/B
- 3-ZA95: 95 W zoned amplifier, 2 LRM spaces
- 3-ZA20B and 3-ZA40B: Class B versions
FAQ
How many audio channels can the 3-ZA20A play?
It receives all eight EST3 digital audio channels and places any one of them on its speaker circuit, with channel selection controlled by network software.
Which speaker voltage does it use?
The built-in speaker circuit is selectable for 25 or 70 VRMS output, wired Class A or Class B.
Does it have a NAC as well?
Yes. It includes a 3.5 A, 24 VDC power-limited notification appliance circuit.
What happens if the audio source fails?
An integral backup tone generator provides a 1 kHz temporal (3-3-3) evacuation tone.