Eaton Wheelock MT4-115-WH-VFR — 120 VAC multitone horn strobe with a red housing, FIRE lettering and a white lens.
The MT4-115 series runs straight from a 120 VAC supply instead of a 24 VDC notification appliance circuit, which suits retrofits and standalone signalling where no panel NAC is available. Eight field-selectable tones cover the common evacuation and alerting patterns without extra equipment.
- The 115 in the model denotes 120 VAC operation, not a candela value
- Fixed 15 cd LED strobe meeting the NFPA 2016 20 ms pulse duration requirement
- Eight tones: horn, bell, march time horn, Code-3 horn, Code-3 tone, slow whoop, siren and hi/lo
- High and Standard levels, horn 89 dBA and 86 dBA reverberant at 10 ft
- Maximum RMS current 0.050 A high, 0.045 A standard
- Certified to UL 464 and UL 1638, ULC S525 and ULC S526
MT4-115-WH-VNS is the grey version with no lettering, while MT4-115-R and MT4-115-S are horn only with no strobe. Do not substitute the 12/24 VDC MT-12/24 or MT-24MCW multi-candela models, which will not run from 120 VAC.
FAQ
Does the MT4-115-WH-VFR need a 24 VDC NAC?
No. The MT4-115 series operates on 120 VAC input.
How many tones are available?
Eight field-selectable tones: horn, bell, march time horn, Code-3 horn, Code-3 tone, slow whoop, siren and HI/LO, with HIGH or STANDARD output levels.
Can it be installed outdoors?
Yes. It is a wall-mount appliance for indoor and outdoor use when installed with the specified back boxes, rated -40°F to 150°F at 95% RH.
Can the horn and strobe be activated separately?
Yes. It has separate input terminals for the audible and the strobe, and shunt wires are included for simultaneous activation from one input circuit.