E2S D1XS2FDC024CS1A1R — D1xS2F flare re-entrant alarm horn sounder, 24 VDC, red marine-grade aluminium, two 3/4" NPT entries, stainless bracket.
This is a configured ordering string, not a catalogue number, and each block is defined in the E2S part-code table: D1xS2 the sounder, F the flare re-entrant horn, DC024 the 11.5 to 54 VDC supply, C the 3/4" NPT entries, S a stainless stopping plug, 1 an A4 316 bracket, A the SIL1 and SIL2 Route 2H version and R red.
- Up to 123 dB(A) at 1 m on high power with tone 4; 118 dB(A) on nominal tone 44
- 64 selectable alarm tones, four remotely switched alarm stages
- 24 VDC current 324 mA default power, 740 mA high power; inrush 815 mA
- Class I Div 1 ABCD T4A and Class I Zone 1 IIC T4A, ambient -55 to +85 °C
- Type 4, 4X, 3R and 13 and IP66/67; 4.00 kg (8.80 lb)
- The DC build is certified to UL 464 and CAN/ULC-S525 for fire alarm use
One letter away sits D1xS2H, the same enclosure with the other horn at 127 dB(A) maximum. D1xS2FAC230 is the 100 to 240 VAC build and holds only the UL 464A general-signalling listing, not the fire alarm listings this DC unit carries.