DITEK DTK-DR5F — 5 V low-voltage DIN rail surge protector with a field-replaceable protection module.
Low-voltage signaling and control conductors that leave a building pick up induced surges long before the 120 V service does. This unit clips onto the panel's own 35 mm rail, so the clamp sits at the enclosure boundary. A hybrid SAD and GDT design protects two circuit pairs in differential (L-L) and common (L-G) mode. A compromised module opens the circuit instead of shorting it.
- Service voltage 5 V; MCOV 6 V; clamping voltage 8 V
- Surge current rating 20,000 A; failure mode open circuit
- Max continuous current 1 A; terminals 30–12 AWG
- ABS housing UL94-V0, IP20; 4.01" × 0.48" × 2.93"
- -40° to 158°F, up to 95% RH non-condensing
- UL 497B certified
Order by circuit voltage — the suffix is the rating. The 5F suits 5 V circuits only; 12, 24, 36, 48, 75 and 130 V circuits take DR12F through DR130F. A 5F across a 24 V NAC or SLC sits far above its 6 V MCOV and will not stay in service.