Det-Tronics X3301A4N14T1 (part number 028262-001) is an X3301 multispectrum infrared flame detector in a copper-free aluminum housing with four 3/4 in. NPT conduit entries and the Eagle Quantum Premier (EQP) output. Three IR sensors and their signal processing give detection of fires from light to heavy hydrocarbon fuels with a high degree of false alarm rejection, and the detector carries Division and Zone explosion-proof ratings for indoor and outdoor use.
The model code breaks down as A = aluminum, 4N = four 3/4 in. NPT entries, 14 = EQP output, T = SIL/FM/CSA/ATEX/IECEx approvals and 1 = Division/Zone Ex d e. The EQP model communicates with the Eagle Quantum Premier controller over the LON/SLC digital loop; analog, relay, RS-485 and HART outputs are not available on this version.
Specifications
| Detector type |
Multispectrum infrared (three IR sensors) |
| Output |
Eagle Quantum Premier LON/SLC, 78.5 kbps |
| Operating voltage |
24 VDC nominal (18 to 30 VDC) |
| Power consumption |
4 W at 24 VDC without heater; heater 8 W max |
| Cone of vision |
90° horizontal |
| Methane fire range |
100 ft (30.5 m) on and off axis, very high setting |
| Operating temperature |
-40°F to +167°F (-40°C to +75°C) |
| Enclosure |
Copper-free aluminum, Type 4X, IP66/IP67 |
| Conduit entries |
Four 3/4 in. NPT |
| Shipping weight |
7 lb (3.2 kg) |
| Warranty |
5 years |
Features
- Automatic Optical Integrity (oi) test once per minute; no external test lamp required
- Microprocessor-controlled heated optics for moisture and ice resistance
- Tri-color LED shows normal, fire and fault status
- Data logging of events
- Typical response time under 10 seconds
Related models
- X3301 with output type 11 (relay), 13 (relay and 0-20 mA), 15 (relay and pulse) or 23 (HART, relay and 0-20 mA).
- 007290-002 Q9033A aluminum mounting arm, for aluminum detectors.
- 007290-001 Q9033B stainless steel mounting arm.
Documents
FAQ
What does X3301A4N14T1 mean?
Aluminum housing (A), four 3/4 in. NPT entries (4N), Eagle Quantum Premier output (14), SIL/FM/CSA/ATEX/IECEx approvals (T) and Division/Zone Ex d e classification (1).
Does this model have relay or 4-20 mA outputs?
No. The EQP model communicates over the LON/SLC loop to an Eagle Quantum Premier system; analog and relay outputs are not available.
Does it need a test lamp?
No. The automatic Optical Integrity feature runs a calibrated performance test once per minute, and testing with an external test lamp is not required.
What supply voltage does it need?
24 VDC nominal, with 18 VDC minimum at the detector and 30 VDC maximum.