Det-Tronics 226166-014 is a calibration gas cylinder holding methane at 2.2% by volume, which equals 50% LFL. The 226166-xxx series is the 50% LFL calibration gas used in Det-Tronics PointWatch calibration kits, and this cylinder is the methane 2.2% version used to calibrate and bump test combustible gas detectors that are calibrated on methane.
Specifications
| Gas |
Methane |
| Concentration |
2.2% by volume |
| Level |
50% LFL |
| Part series |
226166-xxx, 50% LFL calibration gas |
| Matching kit |
006468-014, methane 50% LFL, 2.2% by volume |
Installation notes
- The PIR9400 calibration kit combines the gas with a calibration nozzle (102821-001), regulator and tubing
- The detector must be calibrated with the gas it is set up to monitor; match the cylinder concentration to the setting in the detector manual
- Use the nozzle or calibration port cover on the detector to apply the gas during calibration