Multispectrum Infrared Flame Detector
The Det-Tronics X3301A4N23T2 (028248-001) is an X3301 Multispectrum Infrared Flame Detector. It delivers benchmark hydrocarbon fire detection with strong false-alarm rejection.
Key specifications
- Type: multispectrum infrared (MSIR) flame detector
- Housing: copper-free aluminum
- Conduit entries: 4 x 3/4" NPT
- Output: HART, relay and 0-20 mA outputs
- Approvals: SIL 2, FM, CSA, QPS, ATEX and IECEx
- Area rating: Division/Zone Ex d
- Detection range: up to ~125 ft (38 m) on-axis range to methane
Features
- Advanced signal processing on a 32-bit microprocessor for strong false-alarm rejection
- Microprocessor-controlled heated optics for wet and cold environments
- Continuous automatic optical integrity (oi) checking - no test lamp required
- Event data logger with time/date stamping
- Terminal block supports Class X pathway designation per NFPA 72
Applications: offshore oil & gas platforms, gas turbines, aircraft hangars and automotive paint spray booths.
Documents
FAQ
What does the model code X3301A4N23T2 mean?
Per the X3301 model matrix: A = aluminum housing, 4N = four 3/4 in. NPT ports, 23 = HART, relay and 0-20 mA outputs, T = SIL/FM/CSA/QPS/ATEX/IECEx approvals, and 2 = Division/Zone Ex d classification.
Is a mounting arm required?
Yes. Det-Tronics requires a Q9033 mounting arm: the Q9033A (007290-002) for aluminum detectors only, or the Q9033B (007290-001) for aluminum and stainless steel detectors.
What power does it need?
24 VDC nominal, 18 VDC minimum and 30 VDC maximum. Consumption without the heater is 4 watts at 24 VDC (5.2 watts in alarm); the heater adds up to 8 watts.
Does it need a test lamp?
No. The automatic optical integrity (oi) test checks the optics about once a minute and signals a fault when less than half of the detection range remains; a magnetic or manual oi test can also be run.