Det-Tronics X3301A4N11W2 (part number 028104-035) is an X3301 multispectrum infrared (IR) flame detector for fires from light to heavy hydrocarbon fuels. Its automatic Optical Integrity (oi) feature performs a calibrated performance test once per minute to verify complete detector operation, so testing with an external test lamp is not approved or required.
In the X3301 model matrix, this version is aluminum with four 3/4 in. NPT ports and relay outputs, carries FM/CSA/QPS/ATEX/IECEx approvals, and has a Division/Zone Ex d classification. The detector is suitable for indoor and outdoor use, and a Q9033 mounting arm is required for installation.
Specifications
| Model |
X3301A4N11W2, part number 028104-035 |
| Housing |
Aluminum, 4 ports, 3/4 in. NPT |
| Outputs |
Relay (fire alarm relay Form C, 5 A at 30 VDC) |
| Approvals |
FM, CSA, QPS, ATEX, IECEx |
| Classification |
Division/Zone Ex d |
| Operating voltage |
24 VDC nominal (18 to 30 VDC), 2 V p-p ripple max |
| Power |
4 W at 24 VDC without heater; 17 W at 30 VDC with heater on maximum |
| Power up |
Ready to indicate alarm after 30 seconds |
Installation notes
- A Q9033 mounting arm is required: Q9033A (007290-002) for aluminum detectors, or Q9033B (007290-001)
- Use the X3301 model matrix to match material, threads, outputs and approvals
- Accessories include air shields, a weather shield, FOV limiters and a laser aimer
- Keep a complete spare on hand for field replacement
Related models
- X3302 multispectrum IR flame detector for hydrogen fires, such as the X3302A4N23T1 (029032-001)
- X3301A4N11W1 (028100-034)
Documents
FAQ
What do the characters in X3301A4N11W2 mean?
Per the X3301 model matrix: A is aluminum, 4N is four 3/4 in. NPT ports, 11 is relay outputs, W is FM/CSA/QPS/ATEX/IECEx approvals, and 2 is the Division/Zone Ex d classification.
Is a mounting arm included?
No. A Q9033 mounting arm is required: the Q9033A for aluminum detectors only, or the Q9033B for aluminum and stainless steel detectors.
Do I need a test lamp?
No. The automatic oi feature tests the detector once per minute; testing with an external test lamp is not approved or required.
What supply voltage does it need?
24 VDC nominal, 18 VDC minimum and 30 VDC maximum, with no more than 2 V peak-to-peak ripple.