Det-Tronics UD10S5N28W2C — FlexVu explosion-proof universal display unit, DCU emulator, part 010254-008.
The UD10 puts a backlit, heated LCD at the gas detector, showing level, type and units, and its LON board passes the digitised 4–20 mA value to an Eagle Quantum Premier controller as a process variable. Magnets drive menu and calibration through the sealed housing.
- Code: S 316 stainless, 5N five 3/4 in. NPT ports, 28 EQP/DCU emulator, W FM/CSA/ATEX/CE/IECEx, 2 Ex d, C CGS board
- 24 Vdc nominal, 18 to 30 Vdc; 1.3 W nominal, to 10 W at 30 Vdc on the CGS build with heater and backlight
- Heater cuts in below –10°C; range –40°C to +75°C, 5 to 95% RH
- FM and CSA Class I Div. 1 Groups B, C, D (T5); Type 4X, IP66, no conduit seal
- Terminals 14 to 18 AWG; shipping weight 10.5 lb (4.76 kg) stainless
- Takes GT3000, PIR9400, PIRECL, CGS, AC100/ATX10, PIRDUCT or LS2000, or any linear 4–20 mA sensor
Sensor and termination box are ordered separately: this is the display, not a detector. A is the aluminium housing, 5M the M25 thread, 25 the relay/RS485/HART build.
Documents
FAQ
What does the UD10 DCU Emulator do?
Its LON interface board digitizes the 4–20 mA signal from the attached sensor or transmitter and sends the value as a process variable over the LON to an Eagle Quantum Premier controller.
Which detectors can it be used with?
Det-Tronics GT3000, PIR9400, PIRECL, PIRECL CO2, CGS (with the CGS interface board), AC100/ATX10, PIRDUCT or LS2000, as well as generic linear 4–20 mA sensors.
Is a conduit seal required?
No. The FM approval for Class I, Div. 1, Groups B, C and D states that a conduit seal is not required.
How is it calibrated without opening the housing?
A magnet operates the four internal magnetic switches for calibration and menu navigation, so the hazardous area does not need to be declassified.