Det-Tronics 005434-004 (DE5434-004) is the replacement electrochemical sensor cell for hydrogen sulfide (H2S), 0 to 50 ppm range, used in the C7064E detector. The cell uses capillary diffusion barrier technology and is highly specific to H2S, with little cross-sensitivity to common gases.
Specifications
| Part number |
005434-004 (DE5434-004) |
| Gas |
Hydrogen sulfide (H2S) |
| Range |
0 to 50 ppm |
| Fits |
C7064E detector housing |
| Detector accuracy |
±10% of applied gas or ±3 ppm, whichever is greater |
| Detector response time |
T20 ≤ 12 s, T50 ≤ 30 s |
| Detector stability |
Zero < 1 ppm/month; span < 1% FS/month |
| Weight |
2 oz (0.09 kg) |
Installation notes
- The cell is not field repairable; replace it when calibration can no longer be performed
- De-classify the area or remove power before replacing the sensor in a hazardous area
- Keep the cell in its sealed bag in a cool place until commissioning
- Check the hydrophobic filter (004532-002) before replacing the cell
- Calibrate 24 hours after power-up, one week later, then about every 30 days
The other C7064E ranges use 005434-003 (0 to 20 ppm) and 005434-002 (0 to 100 ppm). Scale the 4-20 mA input to match the cell range.