Autronica 116-BS-420G/GB-G — BS-420G integrated fire and gas alarm control panel kit from the AutroSafe 4 IFG range, supplied as a cabinet to be populated.
It is a full function operating panel for one or several operation zones, driven from a 16 line by 40 character display and a backlit keypad, and it talks to other panels over AutroNet, an Ethernet network. A United States buyer should note this is a European and marine line, certified to the CEN EN 54 series and to marine rules, not to UL 864.
- Kit contains cabinet, panel front, power supply module, communication module and text foils
- Holds up to 12 modules, of which up to 6 may be loop drivers (BSD-310, BSD-311, BSD-330)
- 512 detectors and manual call points per panel, 127 loop units per loop
- 2 Ethernet ports, 2 USB host ports, AutroFieldBus interface
- Nominal 27.2 VDC supply, 18 to 32 VDC
- Certificates Autronica lists include FM, Intertek under the CPR, the US Coast Guard and DNV
Two things to check. The kit ships with no loop driver modules, so a live detection loop needs a BSD-310 or BSD-311 too. And SIL2 belongs to a different number: Autronica lists 116-BS-420G2 as the IEC 61508 SIL2 kit, and 116-BS-420 as the fire-only panel.