Autocall A4099-5214 Pull Station Single Action (with DIP Switch)
The A4099-5214 is a single-action addressable manual pull station with an integral MX addressable module that reports status changes to the fire alarm control unit. A firm downward pull activates the alarm switch, and the lever stays protruding until the station is reset with a key. The address is set by DIP switch or by Digital Enrollment.
Key Features
- Single-action operation; pull lever protrudes when in alarm
- MX addressable loop communications over a single wire pair
- Hard addressing by DIP switch or soft addressing with Digital Enrollment
- Break-rod supplied for optional use
- Tamper-resistant reset key; lock uses the same key as the Autocall fire alarm cabinet (keys ordered separately)
- Surface or semi-flush mounting on standard electrical boxes
- UL listed to Standard 38
Specifications
| Power and communications |
MX Loop, one address per station |
| Standby / alarm current |
0.043 mA / 4.51 mA |
| Wire connections |
Terminal blocks, 20 to 14 AWG |
| Temperature range |
32 to 120 F (0 to 49 C), indoor |
| Humidity |
Up to 93% RH at 90 F (32 C) |
| Housing |
Red with white raised lettering; Lexan polycarbonate or equal |
| Housing dimensions |
5 in. H x 3 3/4 in. W x 1 in. D (127 x 95 x 25 mm) |
Compatible With
- Autocall A050, A250, 4007ES, 4010ES and 4100ES series FACUs with MX communications