Autocall A4090-5260 MX Monitor ZAM
The A4090-5260 Monitor ZAM (Zone Adapter Module) lets one MX Digital addressable point monitor a conventional initiating device circuit fitted with two-wire initiating devices. Zone device power is supplied separately from the fire alarm control panel or another UL listed power supply. It mounts in a standard 4 in. square electrical box.
Key Features
- Class B monitoring of two-wire initiating devices from a single address
- Zone power supplied separately (24 VDC nominal)
- Hard (DIP switch) or soft (Digital Enrollment) addressing
- Enclosed design that limits dust infiltration
- Screw terminals; LED flashes to indicate communications
- UL listed to Standard 864
Specifications
| ZAM input voltage |
21.9 to 26.4 VDC (24 VDC nominal) |
| ZAM loop current at 24 VDC |
0.28 mA supervisory max; 60 mA alarm max |
| Individual ZAM current |
0.049 mA standby / 5.82 mA alarm |
| Zone supervision resistor |
4.7 k ohm, 1/2 W |
| Wire connections |
Screw terminals, 18 to 14 AWG |
| Dimensions (H x W x D) |
4 1/8 in. x 4 in. x 1 3/8 in. (105 x 102 x 35 mm) |
| Temperature range |
32 to 120 F (0 to 49 C), indoor |
Compatible With
- Autocall 2050, 2250, 4007ES, 4010ES and 4100ES fire alarm control panels with MX communications
- Compatible two-wire detectors per the datasheet chart (includes A4098-5601, A4098-5602, A4098-5611)