Apollo 58000-700MAR Discovery Marine MultiSensor Detector OpticalHeat SIL2
The Discovery Marine Multi-Sensor Detector consists of optical smoke and thermistor temperature sensors which give a combined signal for improved false alarm management.
Key Features
- Reliable fire detection in areas with a very wide temperature range from-40°C to +70°C
- Five operating modes for customised fire detection and enhanced false alarm management
- Drift compensation to ensure constant sensitivity
- A great alternative to Ionisation detectors
- Certified to a broad range of marine approvals and EAC approved
- Assessed and certified for use in a safety function to SIL level 2
Specifications
| Warranty |
10 year |
| Applications |
Bedrooms, Large vessels, Marine |
| Fire Type |
Fast and slow burning fires |
| Heat classification |
A1R |
| Analogue value nominal |
23 |
| Analogue value (- tolerance) |
4 |
| Analogue value (+ tolerance) |
0 |
| Analogue value |
23 +0/-4 |
| Alarm level analogue value |
55 |
| Chamber type |
Chevron |
| Colour |
White |
| Sensor configuration |
Horizontal optical bench housing infra-red emitter and sensor, arranged radially to detect forward scattered light. |
| Weight |
105g |
| Materials housing |
Polycarbonate |
Documents & Downloads
FAQ
Which protocols does it work with?
It is compatible with the XP95, Discovery and CoreProtocol digital communication protocols.
What supply voltage does it need?
17 to 28 VDC on a two-wire, polarity-insensitive supply, with a quiescent current of 400 µA.
What temperature range is it rated for?
It operates from -40°C to +70°C, which suits marine areas with a wide temperature range.
Which marine approvals does it carry?
Apollo lists EN 54-5, EN 54-7, CPR, LPCB, MED, LR, BV, DNV-GL, VNIIPO, CCS and KRS.