Air Products and Controls SL-2000-P is a 4-wire conventional photoelectric duct smoke detector for HVAC supply and return ducts. It detects smoke in moving air so air handlers, fans and blowers can be shut down to stop smoke spreading through the building, and its output contacts can drive horns, strobes, remote indicators and test/reset stations.
It runs on 230 VAC, 115 VAC, 24 VAC or 24 VDC and can be mounted horizontally or vertically. Testing is done with the cover in place: the Test Port Valve accepts aerosol smoke, and the reset switch doubles as an alarm test switch.
Specifications
| Detector type |
Photoelectric, 4-wire conventional, plug-in UL 268 head |
| Operating voltage |
230 VAC, 115 VAC, 24 VAC, 24 VDC |
| Standby current |
230 VAC 12 mA; 115 VAC 22 mA; 24 VAC 55 mA; 24 VDC 14 mA |
| Alarm current |
230 VAC 18 mA; 115 VAC 32 mA; 24 VAC 190 mA; 24 VDC 68 mA |
| Alarm contacts |
2 sets Form C, 10 A @ 115 VAC; 1 set Form A, 2 A |
| Trouble contacts |
1 set Form C, 10 A @ 115 VAC |
| Air velocity |
100 to 4,000 ft/min |
| Ambient temperature |
32°F to 140°F (0°C to 60°C) |
| Humidity |
10% to 85% RH, non-condensing |
| Wiring |
#12 to #22 AWG, solid or stranded |
| Interconnect |
Up to 30 units for common functions |
| Housing |
Gray plastic backbox, clear Makrolon 94V-0 cover |
| Dimensions |
13-1/2 x 4-1/2 x 2-1/4 in. |
| Certifications |
UL and cUL (UL 268A) file S2829; CSFM 3240-1004:105 |
Features
- Tool-less front or rear loading of sampling and exhaust tubes
- Clear cover with four captive thumbscrews and instant cover-removal trouble
- Detector LED: flashing for normal, solid for alarm, off for trouble; green pilot and red alarm indicators on the board
- Magnet test capability, magnet included
- Pre-installed duct gaskets and external mounting tabs, no cover removal to mount
- Compatible with building automation and fire alarm systems
Installation notes
- In the box: detector, FAST-TUBE starter kit, 7 in. exhaust tube, red sampling tube cap, two mounting screws, mounting and labeling templates
- Sampling tubes sized to the duct width are required and purchased separately: STN-1.0 up to 12 in., STN-2.5 for 6 in. to 2.5 ft, STN-5.0 for 2.5 to 5 ft, STN-10.0 for 5 to 10 ft
- Also purchased separately: 3/4 in. conduit fitting and 14 to 24 AWG wire
- Accessories include MSR and MS series remote test/reset stations and the WP-2000 weatherproof enclosure
Documents
FAQ
Are sampling tubes included?
No. The box includes a FAST-TUBE starter kit, 7 in. exhaust tube and red sampling tube cap, but sampling tubes sized to the duct width must be ordered separately (STN-1.0, STN-2.5, STN-5.0 or STN-10.0).
What voltages does it accept?
230 VAC, 115 VAC, 24 VAC or 24 VDC.
Can it be tested without removing the cover?
Yes. The Test Port Valve allows aerosol smoke testing with the cover on, the reset switch also works as an alarm test switch, and a test magnet is included.
What airflow range is it rated for?
100 to 4,000 ft/min, at ambient temperatures from 32°F to 140°F (0°C to 60°C).