Altronix AL1002ULADA — 10 A, 24 VDC NAC power extender in a red wall-mount enclosure.
A NAC power extender adds notification appliance power to a fire alarm control panel. Panel NAC outputs drive its inputs; it repeats them on its own supervised circuits from its own 120 VAC supply and batteries, reporting loop trouble back through the steered input.
- 24 VDC power-limited outputs, 10 A total alarm current, 2.5 A per output, plus a separate 1 A battery-backed auxiliary output
- Four Class B, two Class A, or one Class A and two Class B outputs
- Two Class A or Class B FACP inputs, 8 to 30 VDC, for 12 or 24 VDC panels, plus two NC dry contact trigger inputs
- Steady, Temporal Code 3 or input follower; sync for Potter/Amseco, Gentex, System Sensor and CooperWheelock
- Input 120 VAC, 60 Hz, 5 A; enclosure 15.5 × 12.23 × 4.5 in., holds two 12 V 12 Ah batteries, sold separately
- UL 864, FM, CSFM and NYC Department of Buildings (MEA); 32 to 120 °F
Included: power supply, red enclosure, cam lock, battery leads and a 2.2K end-of-line resistor. Same series: AL602ULADA (6.5 A), AL802ULADA (8 A); R1002ULADA is the 10 A rack-mount version.
Documents
FAQ
Will it work with my fire alarm panel?
Altronix states it may be connected to any 24 volt fire alarm control panel. Its inputs accept 8 to 30 VDC, so it works with 12 VDC or 24 VDC panels, plus two NC dry contact trigger inputs.
How many notification circuits does it provide?
Four Class B, two Class A, or one Class A and two Class B supervised indicating circuits, each rated 2.5 A, with 10 A total alarm current and a 1 A auxiliary output.
Can it synchronize strobes?
Yes. Sync protocols include Potter/Amseco, Gentex, System Sensor and CooperWheelock, and a 2-wire horn/strobe sync mode lets horns be silenced while strobes keep flashing.
Are batteries included?
No. Batteries are sold separately; the enclosure holds up to two 12 VDC, 12 AH batteries.