{"title":"Relays","description":"\u003ch2\u003eExplore dependable relays for seamless integration and control in fire alarm and electrical systems\u003c\/h2\u003e\n\u003cp\u003eBuilt for reliability and performance in commercial and industrial applications.\u003c\/p\u003e\n\u003cp\u003eShop high-quality relays today!\u003c\/p\u003e","products":[{"product_id":"system-sensor-eolr-1-end-of-line","title":"System Sensor EOLR-1 End of Line Supervision Relay, SPST Normally Open, 9 to 40 VDC","description":"\u003cp\u003e\u003cstrong\u003eSystem Sensor EOLR-1\u003c\/strong\u003e — epoxy-encapsulated SPST normally open end-of-line supervision relay.\u003c\/p\u003e\u003cp\u003eDespite the end-of-line name this is an active relay, not a passive resistor. Its coil is held energised by the supply it watches, so losing that supply drops the contacts. That lets a fire alarm system supervise a power supply or auxiliary circuit and report its loss, which a terminating resistor cannot do.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eSingle pole single throw normally open contacts\u003c\/li\u003e\n\u003cli\u003eOperating voltage 9 to 40 VDC, or 9 to 35 Vrms on unfiltered full-wave-rectified supplies\u003c\/li\u003e\n\u003cli\u003eOperating current 20 mA maximum\u003c\/li\u003e\n\u003cli\u003eContact ratings 120 VAC at 0.5 A and 30 VDC at 3 A, resistive load\u003c\/li\u003e\n\u003cli\u003e–22°F to 140°F (–30°C to 60°C), 10 to 93 percent RH non-condensing\u003c\/li\u003e\n\u003cli\u003e0.91\" H × 1.65\" W × 1.22\" D; leads 8\" minimum, red and black power in, two violet for relay common and normally open\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eDo not substitute a plain end-of-line resistor such as a 47 kΩ device: a resistor terminates a circuit, while the EOLR-1 switches a dry contact. It ships with wire nuts, tape and a screw.\u003c\/p\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":43132758032608,"sku":"EOLR-1","price":26.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/system-sensor-relays-default-title-system-sensor-eolr-1-end-of-line-31897170018528.jpg?v=1763278700"},{"product_id":"system-sensor-pr-1-epoxy-encapsulated","title":"System Sensor PR-1 Epoxy Encapsulated","description":"\u003ch2\u003eSystem Sensor PR-1 Epoxy Encapsulated (SPDT) Relay With Activation LED\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003ePR-1: Multi-Voltage Relay · Epoxy encapsulated · Single-Pole · Double-Throw · Activation LED\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fan and damper assembly control, door control, air handling unit controls, and other types of system interfacing. They are single-pole, double-throw relays that use a red LED as a visible indication of relay coil energization.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003cli\u003eTerminal strip field wiring connections, mounting track, and hardware\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/I56-2611.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePR-1A Multi-Voltage Relay Installation Guide\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/PR-1_Manual_I56-2191.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePR-1 Multi-Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":43132758851808,"sku":"PR-1","price":19.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/system-sensor-relays-default-title-system-sensor-pr-1-epoxy-encapsulated-31897189646560.jpg?v=1763278714"},{"product_id":"system-sensor-pr-2-epoxy-encapsulated","title":"System Sensor PR-2 Epoxy Encapsulated","description":"\u003ch2\u003eSystem Sensor PR-2 Epoxy Encapsulated (SPDT) Relay with Activation LED\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003ePR-2: Multi-Voltage Relay · Epoxy Encapsulated · Single-Pole · Double-Throw · 10 to 40V DC\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fan and damper assembly control, door control, air handling unit controls, and other types of system interfacing. They are single-pole, double-throw relays that use a red LED as a visible indication of relay coil energization.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003cli\u003eTerminal strip field wiring connections, mounting track, and hardware\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/moved-ss\/PR-2_PR-3_Manual_I56-2192.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePR-2-PR-3 Multi-Voltage Relay\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/I56-2612.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePR-2A-PR-3AMulti-Voltage Relay Installation Guide\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/PR-2_PR-3_Manual_I56-2192.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePR-2-PR-3 Multi-Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":43132758884576,"sku":"PR-2","price":18.3,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/system-sensor-fire-alarms-default-title-system-sensor-pr-2-epoxy-encapsulated-31897190138080.jpg?v=1763278729"},{"product_id":"siemens-crc-6-500-033250-control-relay-card","title":"Siemens CRC-6 (500-033250) Controllable Relay Card, Six Form C Relays, for CC-5 or CC-2 Card Cage","description":"\u003cp\u003e\u003cstrong\u003eSiemens CRC-6\u003c\/strong\u003e (500-033250) — Controllable Relay Card with six programmable Form C relays for FireFinder XLS, Desigo Fire Safety Modular and Cerberus PRO Modular panels.\u003c\/p\u003e\u003cp\u003eIt controls auxiliary building functions such as door-holder release, elevator capture, smoke control and lock release. The card plugs into one slot of a CC-5 or CC-2 card cage and takes an HNET address (001–251) on three rotary switches; field wiring lands on the card cage terminal blocks.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eSix SPDT (Form C) contacts: 4 A at 30 VDC\/120 VAC resistive, 3.5 A at 120 VAC inductive (0.6 PF)\u003c\/li\u003e\n\u003cli\u003eSupervised relay coils; a blinking relay LED indicates coil failure\u003c\/li\u003e\n\u003cli\u003e24 V backplane current 10 mA plus 20.5 mA per active relay; standby 51 mA plus 20.5 mA per active relay\u003c\/li\u003e\n\u003cli\u003eLEDs for power, card fail, HNET fail, 24V fail (below 18 VDC) and each relay\u003c\/li\u003e\n\u003cli\u003eUL 864 and CAN\/ULC-S576 listed; FM, CSFM and NYC Fire Department approved\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eCard only: the CC-5 or CC-2 card cage is separate. Siemens warns that a slot previously wired for a ZIC-4A can short the PSC-12 or PSX-12 24 V output, so remove that wiring first.\u003c\/p\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":43132761112800,"sku":"CRC-6","price":221.2,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/siemens-relays-default-title-siemens-crc-6-500-033250-control-relay-card-31896940445920.jpg?v=1763278776"},{"product_id":"simplex-2088-9021-relay-pam-1","title":"Simplex 2088-9021 Relay PAM-1","description":"\u003cp\u003e\u003cstrong\u003eSimplex 2088-9021\u003c\/strong\u003e — encapsulated SPDT multi-voltage control relay (PAM-1) with coil status LED.\u003c\/p\u003e\u003cp\u003eReach for this when an auxiliary function has to be switched from an existing panel output without burning an addressable point. The potted body accepts 18–35 V AC or DC, 120 VAC or 240 VAC on separate leads, so one part covers both low-voltage and line-voltage circuits; DC inputs are diode polarized. The red LED shows when the coil is energized.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eContacts: SPDT (Form C), 10 A @ 120 VAC resistive\u003c\/li\u003e\n\u003cli\u003eCoil: 18–35 VAC\/VDC, 120 VAC, or 240 VAC\u003c\/li\u003e\n\u003cli\u003eCoil current: 15 mA @ 24 VAC\/VDC and @ 120 or 230 VAC\u003c\/li\u003e\n\u003cli\u003e18 AWG color-coded flying leads\u003c\/li\u003e\n\u003cli\u003e1-1\/2\" H × 1\" W × 7\/8\" D\u003c\/li\u003e\n\u003cli\u003e32° to 120°F; UL 864 Control Unit Accessory\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eNot interchangeable with the 4098-9843 (PAM-SD): the PAM-SD has a polarized 18–32 VDC coil with in\/out wiring, no LED, and contacts rated 7 A @ 28 VDC and 120 VAC plus 250 µA @ 5 VDC. If the drawing calls for supervised in\/out coil wiring or logic-level switching, order 4098-9843.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132773138656,"sku":"2088-9021","price":32.05,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-2088-9021-relay-pam-1-31897022365920.jpg?v=1770199239"},{"product_id":"simplex-4090-9118-relay-iam-with-t-sense","title":"Simplex 4090-9118 Relay IAM with T-Sense","description":"\u003cp\u003e\u003cstrong\u003eSimplex 4090-9118\u003c\/strong\u003e — Relay IAM (Individual Addressable Module) with T-Sense input, IDNet.\u003c\/p\u003e\u003cp\u003eThis module does two jobs on a single IDNet address: it monitors two input contact closures on one point and drives an output relay on the other. That is the reason to specify it over a plain relay module — on a loop where addresses are scarce, it does the work of two devices.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eModule power comes from the IDNet communications channel, so no separate power wiring is required\u003c\/li\u003e\n\u003cli\u003eThe input circuit and the relay operate independently and can be disabled separately\u003c\/li\u003e\n\u003cli\u003eRelay contacts rated 2 A (1 A inductive) at 30 VDC, and 0.5 A (0.25 A inductive) at 120 VAC — non-power-limited\u003c\/li\u003e\n\u003cli\u003eOperating temperature range 32°F to 120°F (0°C to 49°C)\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eFor use with Simplex 4007ES, 4010ES, 4100ES or 4100U fire alarm control panels providing IDNet communications. A 4100U requires software revision 11 or higher.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132775923936,"sku":"4090-9118","price":41.7,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-4090-9118-relay-iam-with-t-sense-31897046745312.jpg?v=1763279038"},{"product_id":"simplex-4090-9119-relay-idnet-2-iam","title":"Simplex 4090-9119 Relay IDNET 2 IAM","description":"\u003ch2\u003eSimplex 4090-9119 Relay IDNET 2 IAM with Feedback\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/YDKyfhjAWucE5gEvdqEEXA\/content\" target=\"_blank\" rel=\"noopener\"\u003e4090-9119 Relay IAM (Individual Addressable Module) with Unsupervised Input\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/4_G3yucWz8atjRii9itYPg\/content\" target=\"_blank\" rel=\"noopener\"\u003eDevice Communications Compatibility Chart\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/PnH3NkFnrl86ts2pkzL2Pw\/content\" target=\"_blank\" rel=\"noopener\"\u003eDispositifs adressables IDNet and MAPNET II\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/PnxUHheBRn20X8youT1MpA\/content\" target=\"_blank\" rel=\"noopener\"\u003eCentre de commande distant InfoAlarm de la gamme 4100 pour le panneau de commande d'alarme d'incendie 4010ES\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132775956704,"sku":"4090-9119","price":36.4,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-4090-9119-relay-idnet-2-iam-31897047138528.jpg?v=1763279024"},{"product_id":"simplex-565-964-4098-2-wire-duct","title":"Simplex 565-964 4098 2-Wire Duct","description":"\u003cp\u003e\u003cstrong\u003eSimplex 565-964\u003c\/strong\u003e — replacement duct interface board for the 4098 two-wire duct detector with relay drive.\u003c\/p\u003e\u003cp\u003eIn the 4098 range the housing samples duct air, a 4098-9601 photoelectric detector does the sensing, and the interface board carries the connection back to the panel. The relay drive version adds a supervised relay output on top of the two-wire initiating circuit, which is how a duct alarm stops the air handler.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eServes the 4098-9688 Two-Wire Duct Detector with Relay Drive\u003c\/li\u003e\n\u003cli\u003eInput 15 to 32 VDC, polarized; standby 2.0 mA, alarm 40 mA, both at 24 VDC max\u003c\/li\u003e\n\u003cli\u003eDrives one 4098-9841 remote relay, coil connections supervised to 100 feet\u003c\/li\u003e\n\u003cli\u003eRemote relay contacts rated 1 A at 28 VDC or 1\/2 A at 120 VAC resistive\u003c\/li\u003e\n\u003cli\u003eOne such detector only per two-wire circuit; not for 4004 or 4005 low current IDCs\u003c\/li\u003e\n\u003cli\u003eDetector removal, loss of 24 VDC or a relay output fault reports trouble at the panel\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eConfirm the housing first. The 4098-9685 is two-wire with no relay output, the 4098-9686 is four-wire and drives fifteen 4098-9843 PAM-SD relays, and the 4098-9755 and -9756 are TrueAlarm housings taking a 4098-9714 sensor instead. No Simplex document we obtained prints 565-964 against a 4098 model number, so check the board marking before ordering.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132791390432,"sku":"565-964","price":45.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-565-964-4098-2-wire-duct-31897132466400.jpg?v=1763279371"},{"product_id":"honeywell-mr-101-cr-24vdc-mr-series-relay-with-spdt","title":"Honeywell MR-101-CR 24VDC MR Series Relay with SPDT","description":"\u003ch2\u003eHoneywell MR-101-CR 24VDC, MR Series Relay with SPDT (10A) contacts\u003c\/h2\u003e\n\u003cp\u003eA single relay may be energized from a voltage source or VAC by wiring to appropriate input terminals.\u003c\/p\u003e\n\u003cp\u003eThe MR-101-CR contains a built-in, red light-emitting diode (LED) which lights up to indicate an energized coil. The relay can be \"snapped apart\" from a standard four-module assembly and used independently.\u003cbr\u003e\u003cbr\u003eThis device is perfectly suited for applications where local contacts are required for system status, remote contacts for control of electrical loads, and general purpose switching.\u003c\/p\u003e\n\u003cp\u003e Ideal for HVAC, Temperature Control, Fire Alarm, Security, Energy Management, and Lighting Control Systems.\u003c\/p\u003e\n\u003cp\u003e\u003ca href=\"https:\/\/thefirealarmsupplier.com\/collections\/honeywell\"\u003eCheck out other Honeywell products.\u003c\/a\u003e\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":43132858368224,"sku":"MR-101\/C\/R","price":33.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/honeywell-relays-default-title-honeywell-mr-101-cr-24vdc-mr-series-relay-with-spdt-31896868520160.jpg?v=1763277470"},{"product_id":"space-age-pam-2-multi-voltage-relay-module","title":"Space Age PAM-2 Multi-Voltage Relay Module","description":"\u003cp\u003e\u003cstrong\u003eAir Products and Controls PAM-2\u003c\/strong\u003e — encapsulated multi-voltage relay module with a single SPDT dry Form-C contact and a red coil-energised LED.\u003c\/p\u003e\u003cp\u003ePAM modules give a fire, security or building control system a remote dry contact for control or status feedback, wherever a panel output has to switch something it cannot drive directly. The body is fully potted and terminates in flying leads rather than screw terminals, so it mounts on the supplied tape or screw, or sits loose in a back box. Both DC inputs are polarised and diode protected.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eCoil energised by either 12 V DC or 24 V DC, drawing 15 mA at both\u003c\/li\u003e\n\u003cli\u003eOne SPDT dry Form-C contact set\u003c\/li\u003e\n\u003cli\u003eRated 7 A at 120 V AC, 7 A at 24 V DC and 250 µA at 5 V DC\u003c\/li\u003e\n\u003cli\u003eTwelve-inch 18 AWG leads, wire nuts included\u003c\/li\u003e\n\u003cli\u003eUL listed S3403, MEA 73-92-E Volume XXI, CSFM 7300-1004:101\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eMatch the suffix to the coil: PAM-1 takes 24 V AC, 24 V DC or 120 V AC and switches 10 A at 120 V AC or 7 A at 24 V DC; PAM-4 spans 12 to 40 V DC and carries no LED; PAM-SD runs on 20 to 32 V DC, switches 7 A and adds a seventh lead so a supervised circuit can pass through it. Space Age Electronics catalogues the identical relay as SSU-PAM-2, under the same listing numbers.\u003c\/p\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43132859810016,"sku":"PAM-2","price":22.5,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-relays-default-title-space-age-pam-2-multi-voltage-relay-module-31896815960288.jpg?v=1771880955"},{"product_id":"system-sensor-r-10t","title":"System Sensor R-10T Relay, SPDT, Multivolt, Track Mount","description":"\u003ch2\u003eSystem Sensor R-10T Multi-Voltage Relay Spdt, Multivolt, Track Mount\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-10T: Multi-Voltage Relay, 1 Form C (SPDT) Relay, Red LED, Track Mount, UL Listed\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/moved-ss\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T-R-20T-R-14T-R-24T Multi Voltage Relay\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T, R-20T, R-14T, R-24T Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":43132861612256,"sku":"R-10T","price":24.3,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/system-sensor-relays-default-title-system-sensor-r-10t-31897192136928.jpg?v=1763277545"},{"product_id":"system-sensor-r-24e-4-gang-relay","title":"System Sensor R-24E 4-Gang Relay","description":"\u003ch2\u003eSystem Sensor R-24E 4-Gang Relay, DPDT, Multivolt, Track Mount, Metal Enclosure\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-24E: Multi-Voltage Relay, 4-Gang 2 Form C (DPDT) Relay with 4 Red Activation LEDs, Steel Enclosure\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage-Relay_Manual_I56-2536.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10E, R-20E, R-14E, R-24E Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":43132862038240,"sku":"R-24E","price":125.65,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/system-sensor-relays-default-title-system-sensor-r-24e-4-gang-relay-31897191350496.jpg?v=1763277561"},{"product_id":"simplex-565-045-1","title":"Simplex 565-045 4100 8 PT Relay Board","description":"\u003ch2\u003eSimplex 565-045 4100 8 PT Relay Board\u003c\/h2\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132889137376,"sku":"565-045","price":198.1,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/simplex-relays-default-title-simplex-565-045-34202016350432.jpg?v=1763278030"},{"product_id":"simplex-2088-9008-mr101-c-relay","title":"Simplex 2088-9008 MR-101\/C SPDT Control Relay, Track Mount with Cover","description":"\u003cp\u003e\u003cstrong\u003eSimplex 2088-9008\u003c\/strong\u003e — MR-101\/C multi-purpose control relay, single SPDT, track mount with cover.\u003c\/p\u003e\u003cp\u003eThis is the relay that hands a fire alarm command to equipment the panel cannot switch directly. Unlike the encapsulated 2088-9021 (PAM-1) and 4098-9843 (PAM-SD), which terminate in flying leads, the MR-101\/C is a track-mounted module with screw terminal blocks and a snap-on cover.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eSingle SPDT (Form C) contacts\u003c\/li\u003e\n\u003cli\u003e10 A @ 120 VAC, N.O. rated 1\/6 HP and N.C. rated 1\/8 HP; 7 A @ 28 VDC and @ 230 VAC\u003c\/li\u003e\n\u003cli\u003eCoil 18–35 VAC\/VDC, 120 VAC or 230 VAC, selected by wiring to the appropriate input terminal; diode polarized for DC\u003c\/li\u003e\n\u003cli\u003eCoil current 18 mA\u003c\/li\u003e\n\u003cli\u003eRed LED indicates the relay energized\u003c\/li\u003e\n\u003cli\u003e5-1\/8\" H × 3-1\/8\" W × 2-1\/2\" D\u003c\/li\u003e\n\u003cli\u003eUL Listed under Standard 864 as a Control Unit Accessory (UOXX)\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eCheck the suffix before ordering. The 2088-9007 (MR-101\/T) is the same SPDT relay without the cover and the 2088-9010 (MR-201\/C) is DPDT in the same covered package. The PAM-SD is not a substitute: 24 VDC polarized only, no LED, 7 A.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132892610784,"sku":"2088-9008","price":37.2,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-2088-9008-mr101-c-relay-31897023414496.jpg?v=1763278055"},{"product_id":"space-age-2088-9009-mr201-relay","title":"Simplex 2088-9009 MR-201\/T Control Relay, DPDT Track Mount with LED","description":"\u003cp\u003e\u003cstrong\u003eSimplex 2088-9009\u003c\/strong\u003e — MR-201\/T multi-voltage control relay, one DPDT position, track mounted.\u003c\/p\u003e\u003cp\u003eFire alarm panels often need a dry contact to hand an event to equipment outside the fire system, such as a damper, a door holder or an elevator recall input. This relay does that: one coil, driven from any of four supply voltages, switching two isolated Form C contact sets.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eOne module position with DPDT dry Form C contacts\u003c\/li\u003e\n\u003cli\u003eCoil takes 18 to 35 VDC, 18 to 35 VAC, 120 VAC or 230 VAC, set by which terminal is wired; DC input is polarized\u003c\/li\u003e\n\u003cli\u003eCoil current 40 mA on DPDT models\u003c\/li\u003e\n\u003cli\u003eContacts rated 10 A at 120 VAC, 1\/6 HP normally open and 1\/8 HP normally closed, plus 7 A at 28 VDC and at 230 VAC\u003c\/li\u003e\n\u003cli\u003eRed LED lights when the coil is energized, so no meter is needed at checkout\u003c\/li\u003e\n\u003cli\u003e3 1\/4 in. H × 2 1\/8 in. W × 1 1\/2 in. D, supplied with snap-track hardware and no cover\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eCheck the ordering table first: 2088-9007 is the same module with SPDT contacts, 2088-9010 is the DPDT version supplied with a cover, and 2088-9019 is the four-position DPDT assembly.\u003c\/p\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43132892774624,"sku":"2088-9009","price":38.85,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-relays-default-title-space-age-2088-9009-mr201-relay-31897022464224.jpg?v=1763278078"},{"product_id":"simplex-2088-9010-mr201-c-relay","title":"Simplex 2088-9010 MR201\/C Relay","description":"\u003cp\u003e\u003cstrong\u003eSimplex 2088-9010\u003c\/strong\u003e — MR-201\/C multi-voltage control relay, DPDT, single position with cover.\u003c\/p\u003e\u003cp\u003ePanels shut down fans, close dampers, drop door holders and recall elevators through auxiliary relays rather than driving those loads directly. The 2088-9010 is the double-pole version, so one panel output transfers two independent circuits. A red LED shows the coil is energized through a viewing port in the cover.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eDPDT contacts 10 A @ 120 VAC (N.O. 1\/6 HP, N.C. 1\/8 HP), 7 A @ 28 VDC and @ 230 VAC\u003c\/li\u003e\n\u003cli\u003eCoil 18–35 VAC\/VDC, 120 VAC or 230 VAC, selected by input terminal; diode polarized for DC\u003c\/li\u003e\n\u003cli\u003eCoil current 40 mA on DPDT models; terminals accept up to 14 AWG\u003c\/li\u003e\n\u003cli\u003e5-1\/8\" H × 3-1\/8\" W × 2-1\/2\" D\u003c\/li\u003e\n\u003cli\u003e32°F to 120°F; UL 864 Control Unit Accessory (UOXX)\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eOn wording: Simplex calls this \u003cem\u003etrack mount with cover\u003c\/em\u003e, while Air Products and Controls, which builds the MR series, calls the same \/C assembly \u003cem\u003eenclosure mounted\u003c\/em\u003e with an 18 gauge backbox and 1\/2 in. knockouts. Dimensions match: one product, two descriptions, and it arrives in its own covered box. Match poles and packaging: 2088-9008 (MR-101\/C) is SPDT in the same housing, 2088-9009 (MR-201\/T) is DPDT on bare track.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132893069536,"sku":"2088-9010","price":56.45,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-2088-9010-mr201-c-relay-31897022857440.jpg?v=1763278055"},{"product_id":"simplex-4090-5203-single-relay-output","title":"Simplex 4090-5203 Single Relay Output","description":"\u003ch2\u003eSimplex 4090-5203 Single Relay Output programmable from the MX Loop\u003c\/h2\u003e\n\u003cp\u003eApplications include signaling fire conditions to plants, machinery, fire doors, dampers, and security systems. The relay coil is monitored. The relay contact is rated for 2A @ 24V DC.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132907061472,"sku":"4090-5203","price":44.5,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-4090-5203-single-relay-output-31897040388320.jpg?v=1763278164"},{"product_id":"simplex-4100-6033-relay-card","title":"Simplex 4100-6033 Relay Card","description":"\u003ch2\u003eSimplex 4100-6033 Relay Card is used to provide common unsupervised control functions or indications for devices such as fans and doors\u003c\/h2\u003e\n\u003cp\u003eEach relay module has three circuits: one each for alarm, trouble, and supervisory signals.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43132923543776,"sku":"4100-6033","price":101.35,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-4100-6033-relay-card-31897076170976.jpg?v=1763278255"},{"product_id":"siemens-xtri-r-s54370-b1-a1-addressable-monitor","title":"Siemens XTRI-R (S54370-B1-A1) Addressable Monitor","description":"\u003cp\u003e\u003cstrong\u003eSiemens XTRI-R (S54370-B1-A1)\u003c\/strong\u003e — addressable single-input intelligent interface module with an on-board Form C relay, used to bring a dry-contact device onto the SLC and to control or shunt external equipment from the same address.\u003c\/p\u003e\n\u003cp\u003eThe XTRI-series interface modules connect direct shorting devices to the fire alarm control panel's signalling line circuit, each taking one address on the loop. The XTRI-R monitors a normally open or normally closed dry contact and adds an addressable Form C relay; relay and input contact share the address but can be controlled as separate functions from a compatible Siemens FACP, which is what makes this the module to use where external equipment has to be shunted or driven. Every XTRI-series module carries built-in ISOtechnology — a configurable dual isolator that meets NFPA 72 Class X (Style 7) wiring requirements, supports up to 252 isolators per loop, and reports whether a short lies in front of or behind the device so the panel can locate the fault instead of just reporting it. Modules can be configured in isolator (polarity sensitive) or non-isolator (polarity insensitive) mode, and compatible panels will flag a module configured as an isolator but wired polarity-insensitive.\u003c\/p\u003e\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003ePart number\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eS54370-B1-A1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eType\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAddressable single-input intelligent interface module with relay; one address per module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eInput\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eOne normally open (N.O.) or normally closed (N.C.) dry contact\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelay\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eAddressable Form C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelay ratings (resistive)\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e4 Amps @ 125 VAC; 4 Amps @ 30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating voltage range\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e13 VDC to 32 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eActive or standby current, max.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e500 µA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eCurrent draw, max.\/avg.\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e750 µA (XTRI-R)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eOperating temperature\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e32°F to 120°F (0°C to 49°C)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eRelative humidity\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eNot greater than 95%, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eWire sizes\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003e18 AWG minimum, 14 AWG maximum\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eIsolation\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eBuilt-in configurable dual isolator (ISOtechnology); up to 252 isolators per loop, up to 30 devices between isolators\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eStatus LED\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eGreen 10 s normal, yellow 4 s trouble, red 1 s locate\/alarm, red 10 s output device active\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003e\u003cstrong\u003eListings\u003c\/strong\u003e\u003c\/td\u003e\n\u003ctd\u003eUL 864, UL 2572, UL 2017 Listed; CAN\/ULC-S527 and CAN\/ULC-S576 Listed, File S24304, Vol. 3; RoHS compliant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\n\u003ch3\u003eInstallation notes\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eIsolator mode changes the wiring rules:\u003c\/strong\u003e configured as an isolator the module is polarity sensitive; configured as a non-isolator it is polarity insensitive. Wiring a module polarity-insensitively while it is configured as an isolator is a real and common mistake, and compatible panels will report it.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eClass X survivability:\u003c\/strong\u003e the built-in dual isolators are what let the loop meet NFPA 72 Class X (Style 7). Observe the limit of 30 devices between isolators when mixing isolated and non-isolated devices.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eMixed device generations:\u003c\/strong\u003e the devices sitting between isolators may be either H-series or the newer X-series detection devices.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eAddress before installing:\u003c\/strong\u003e the DPU (500-033260) device programmer sets and verifies the address and tests module functionality through the programming port.\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eRelay is for external equipment,\u003c\/strong\u003e typically control or shunting — it is not a notification appliance circuit. Respect the 4A resistive rating at 125 VAC \/ 30 VDC.\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eRelated models\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003cstrong\u003eXTRI-S (S54370-B3-A1)\u003c\/strong\u003e — single-input module without the relay; monitors and reports a N.O. or N.C. contact only, 650 µA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eXTRI-D (S54370-B2-A1)\u003c\/strong\u003e — dual-input module supervising two sets of dry contacts on one address, 950 µA\u003c\/li\u003e\n\u003cli\u003e\n\u003cstrong\u003eHTRI-R (500-033300)\u003c\/strong\u003e — the earlier H-series single interface module, without built-in ISOtechnology isolation\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003cp\u003e\u003cem\u003eSpecifications taken from the Siemens data sheet \"Intelligent Device Interface Modules, Model XTRI-D | XTRI-R | XTRI-S,\" document 6167 (October 2020, Rev. 3). Manufacturer specifications are subject to change without notice.\u003c\/em\u003e\u003c\/p\u003e","brand":"Siemens","offers":[{"title":"Default Title","offer_id":43133016211680,"sku":"XTRI-R","price":125.85,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/siemens-relays-default-title-siemens-xtri-r-s54370-b1-a1-addressable-monitor-31896978850016.jpg?v=1763277178"},{"product_id":"simplex-4098-9860-supervised-relay","title":"Simplex 4098-9860 Supervised Relay","description":"\u003ch2\u003eSimplex 4098-9860 Supervised Relay (For use with 4098-9780 Base)\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/AzYjj7n5vTY87bWDlJdo1w\/content\" target=\"_blank\" rel=\"noopener\"\u003eTrueSense يوفر الكشف المبكر عن الحرائق بواسطة TrueAlarm 9764 من - طراز المستشعر المتعدد 4098\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/GwecOuOEhUV6Ehq_P9GdtQ\/content\" target=\"_blank\" rel=\"noopener\"\u003eTrueAlarm Multi-Sensor Model 4098-9764 Providing TrueSense Early Fire Detection\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/kNEOWkZkQrwfcsbhT0TPEA\/content\" target=\"_blank\" rel=\"noopener\"\u003eTrueAlarm Multi-Sensor Model 4098-9754 Providing TrueSense Early Fire Detection\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/_luFsOjDEPcOMZTZEmkcMw\/content\" target=\"_blank\" rel=\"noopener\"\u003eE-Series Analog Heat Sensor 4098-9733E and Bases for Extended Exposure to High Humidity\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/LfzQH2w1LMItm7Vt5XwTcg\/content\" target=\"_blank\" rel=\"noopener\"\u003e4098-9754 提供早期火警偵測功能的 TrueAlarm 複合式感知器\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/vVVIqDJmSmg1po_DAMwkmQ\/content\" target=\"_blank\" rel=\"noopener\"\u003eTrueAlarm Analog Sensors - Photoelectric and Heat; Standard Bases and Accessories\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/NfKZgUVOaafS~3cBv2xN0Q\/content\" target=\"_blank\" rel=\"noopener\"\u003eالتناظرية – مستشعرات كهروضوئية وحرارية؛ قواعد قياسية وملحقات TrueAlarm مستشعرات\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/SmEOZssXHVkKfEhXaa03QA\/content\" target=\"_blank\" rel=\"noopener\"\u003eTrueAlarm 類比感知器 - 光電及熱； 標準底座及配件\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43133020635360,"sku":"4098-9860","price":81.15,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-relays-default-title-simplex-4098-9860-supervised-relay-31897060376800.jpg?v=1763277654"},{"product_id":"space-age-ssu-pam-1-multi-voltage-10a","title":"Space Age SSU-PAM-1 Multi-Voltage Encapsulated Relay, SPDT 10 A, 24VAC 24VDC or 120VAC","description":"\u003cp\u003e\u003cstrong\u003eSpace Age SSU-PAM-1\u003c\/strong\u003e — encapsulated Gator Relays multi-voltage control relay with one SPDT contact set and six flying leads.\u003c\/p\u003e \u003cp\u003eIt puts a set of dry contacts wherever a fire alarm, smoke control or building automation circuit needs one, with no enclosure: the body is potted and ships with a screw, tape and wire nuts. Three of the leads select the coil input, so one part serves 24 Vac, 24 Vdc and 120 Vac. A red LED shows the coil energised.\u003c\/p\u003e \u003cul\u003e\n\u003cli\u003eOne SPDT continuous-duty coil, 10 million cycles mechanical, 8 ms operate time\u003c\/li\u003e\n\u003cli\u003eCoil input 24 Vac, 24 Vdc or 120 Vac at 50 to 60 Hz; pull in 16 Vac or 18 Vdc\u003c\/li\u003e\n\u003cli\u003eCoil current 20 mA at 24 Vdc, 50 mA at 24 Vac and 30 mA at 120 Vac\u003c\/li\u003e\n\u003cli\u003eContacts 10 A general use at 120 Vac; 10 A resistive at 30 Vdc normally open, 7 A normally closed\u003c\/li\u003e\n\u003cli\u003eSix leads, 12 in., 600 V rated; body 1.5 × 1.2 × 1.2 in.\u003c\/li\u003e\n\u003cli\u003eUL 864 and UUKL smoke control, C-UL, CE, RoHS and CSFM\u003c\/li\u003e\n\u003c\/ul\u003e \u003cp\u003eSSU-PAM-2 and SSU-PAM-4 are the 9 to 40 Vdc versions, SSU-PAM-SD the 20 to 32 Vdc one and SSU-PAM-EOLR the SPST one. The Air Products and Controls PAM-1 shares the name and is a different part under a different listing file.\u003c\/p\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43133107241184,"sku":"SSU-PAM-1","price":19.7,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-relays-default-title-space-age-ssu-pam-1-multi-voltage-10a-31897146097888.jpg?v=1763279916"},{"product_id":"fire-lite-mr-201-t-mr-series-multivoltage-control-relay","title":"Fire-Lite MR-201\/T MR Series Multivoltage Control Relay","description":"\u003ch2\u003eFire-Lite MR-201\/T MR Series Multivoltage Control Relay, DPDT, Track Mount\u003c\/h2\u003e","brand":"Fire-Lite","offers":[{"title":"Default Title","offer_id":43133143449824,"sku":"MR-201\/T","price":32.15,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/fire-lite-relays-default-title-fire-lite-mr-201-t-mr-series-multivoltage-control-relay-31896817271008.jpg?v=1770202350"},{"product_id":"space-age-ssu-mr-201-c-r-multi-voltage-control-relay","title":"Space Age SSU-MR-201\/C\/R MR-200 Series Multi-Voltage Control Relay, DPDT, Red Enclosure","description":"\u003cp\u003e\u003cstrong\u003eSpace Age SSU-MR-201\/C\/R\u003c\/strong\u003e — single-position MR-200 Series multi-voltage control relay, DPDT contacts, in a backbox under a red cover.\u003c\/p\u003e\u003cp\u003eOne relay accepts any of four control voltages: wire the coil to the matching input terminal and the same part serves a 24 V panel output, a 120 VAC circuit or a 230 VAC circuit. A red LED lights when the coil is energized.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eCoil accepts 24 (18 to 35) VDC, 24 VAC, 120 VAC or 230 VAC; DC input polarized\u003c\/li\u003e\n\u003cli\u003eOne module position, dry Form C DPDT contacts\u003c\/li\u003e\n\u003cli\u003eContacts rated 7 A at 28 VDC, 10 A at 120 VAC, 7 A at 230 VAC\u003c\/li\u003e\n\u003cli\u003e40 mA per position; continuous duty at 24 VAC, 24 VDC or 120 VAC, not at 230 VAC\u003c\/li\u003e\n\u003cli\u003eEnclosure 5.125\" H × 3.125\" W × 2.50\" D, 18ga steel backbox, 1\/2\" knockouts\u003c\/li\u003e\n\u003cli\u003eTerminals take #14 to #22 AWG; rated 32 to 120 °F\u003c\/li\u003e\n\u003cli\u003eUL listed as a Control Unit Accessory and for UUKL smoke control\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe suffixes carry the whole difference. SSU-MR-201\/C is the same relay under a grey cover, SSU-MR-201\/T is track-mounted with no enclosure, SSU-MR-204\/C\/R has four positions, and SSU-MR-101\/C\/R is the SPDT relay of the MR-100 line.\u003c\/p\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43133143679200,"sku":"SSU-MR-201\/C\/R","price":42.5,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-control-relay-default-title-space-age-ssu-mr-201-c-r-multi-voltage-control-relay-31897149047008.jpg?v=1763280312"},{"product_id":"space-age-ssu-mr-101-c-r-series-multi-voltage","title":"Space Age SSU-MR-101\/C\/R Series Multi-Voltage","description":"\u003ch2\u003eSpace Age SSU-MR-101\/C\/R Series Multi-Voltage Control Relay, 10A\u003c\/h2\u003e\n\u003cp\u003eThe MR 100 Series Multi-Voltage Control Relays offer SPDT resistive contacts which may be operated by one of four input control voltages. A single relay may be energized from a voltage source of 24VDC, 24VAC, 120VAC or 230VAC by wiring to appropriate input terminals.\u003cbr\u003e\u003cbr\u003eEach relay position contains a red LED which indicates the relay coil is energized. Relays may be from a standard 4 module assembly and used independently. These devices are ideal for applications where local contacts are required for system status, remote contacts for control of electrical loads and general purpose switching. They are suitable for use with HVAC, temperature control, fire alarm, security, energy management and lighting control systems.\u003c\/p\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43133148692704,"sku":"SSU-MR-101\/C\/R","price":34.85,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-relays-default-title-space-age-ssu-mr-101-c-r-series-multi-voltage-31897150095584.jpg?v=1763280390"},{"product_id":"honeywell-mr-101-t-spdt-track-mount","title":"Honeywell MR-101\/T SPDT Track Mount","description":"\u003cp\u003e\u003cstrong\u003eHoneywell MR-101\/T\u003c\/strong\u003e — MR-100 Series multi-voltage control relay, one SPDT position, track mounted, built by Air Products and Controls.\u003c\/p\u003e\u003cp\u003eLife safety and building control panels need an isolated dry contact to pass an event to equipment outside the panel: fan shutdown, damper control, door release or elevator recall. This relay provides one, with a coil that accepts any of four common supply voltages.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eOne module position with SPDT dry Form C contacts\u003c\/li\u003e\n\u003cli\u003eCoil takes 18 to 35 VDC, 18 to 35 VAC, 120 VAC or 230 VAC, set by which terminal is wired; DC input is polarized\u003c\/li\u003e\n\u003cli\u003eCoil current 18 mA per position on MR-100 Series units\u003c\/li\u003e\n\u003cli\u003eContacts rated 10 A at 120 VAC, 1\/6 HP normally open and 1\/8 HP normally closed, plus 7 A at 28 VDC and at 230 VAC\u003c\/li\u003e\n\u003cli\u003eRed LED confirms the coil is energized; relays rated for 10,000,000 mechanical operations\u003c\/li\u003e\n\u003cli\u003e3 1\/4 in. H × 2 1\/8 in. W × 1 1\/2 in. D, supplied with a 3 1\/2 in. wide snap track\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe suffix is the whole difference: \/C is the same relay in a dust-resistant enclosure, \/C\/R adds a red cover for New York City, MR-104\/T is the four-position version, and MR-201\/T is the DPDT relay.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":43133150003424,"sku":"MR-101\/T","price":19.15,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/honeywell-relays-default-title-honeywell-mr-101-t-spdt-track-mount-31896817959136.jpg?v=1763280750"},{"product_id":"space-age-ssu-mr-818-t-relay-24-vac-dc-120vac","title":"Space Age SSU-MR-818\/T Relay 24 VAC\/DC 120VAC","description":"\u003ch2\u003eSpace Age SSU-MR-818\/T Relay (Q8)TRCK 24 VAC\/DC 120VAC 10A Polarized\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eEight-position MR-810 Series relay module on snap track. Each position is an SPDT relay with a 10 A fuse on the common contact, a polarized diode-protected control input and a red LED that lights when the coil is energized. Positions can be snapped apart from the 8-module assembly and used on their own.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e8 relay positions, SPDT (Form C) contacts each\u003c\/li\u003e\n\u003cli\u003e10 A field replaceable fuse on each common contact\u003c\/li\u003e\n\u003cli\u003eRed LED per position shows coil energized\u003c\/li\u003e\n\u003cli\u003ePolarized, diode protected input\u003c\/li\u003e\n\u003cli\u003eSupplied with 3.5\" wide low profile snap track and mounting screws\u003c\/li\u003e\n\u003cli\u003ePositions can be snapped apart\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eSpecifications\u003c\/h3\u003e\n\u003ctable class=\"ths-spec-table\"\u003e\u003ctbody\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eModule positions\u003c\/th\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eCoil\u003c\/th\u003e\n\u003ctd\u003e24 VDC @ 20 mA or 24 VAC @ 63 mA per position\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003ePick-up \/ drop-out\u003c\/th\u003e\n\u003ctd\u003e19.2 VDC \/ 3.6 VDC (26.4 VDC max)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eContact rating\u003c\/th\u003e\n\u003ctd\u003e10 A resistive @ 24 VDC \/ 250 VAC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eFuse\u003c\/th\u003e\n\u003ctd\u003e10 A, 0.25\" dia. x 0.75\" L\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eTrack mounted size\u003c\/th\u003e\n\u003ctd\u003e3.45\" H x 8.50\" W x 1.07\" D\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eWiring terminals\u003c\/th\u003e\n\u003ctd\u003e#14 to #22 AWG, solid or stranded\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003cth scope=\"row\"\u003eEnvironment\u003c\/th\u003e\n\u003ctd\u003e32°F to 120°F, 85% RH non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\u003c\/table\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/www.1sae.com\/media\/assets\/product\/documents\/lt10512.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMR-810 Series 10A Fused Relays Data Page LT10512\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/www.1sae.com\/media\/assets\/product\/documents\/mr-810-install.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMR-810 Series Installation Guide\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":43133151576288,"sku":"SSU-MR-818\/T","price":152.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/space-age-relays-default-title-space-age-ssu-mr-818-t-relay-24-vac-dc-120vac-31897146720480.jpg?v=1763280404"},{"product_id":"fire-lite-pam-4-10a-form-c-relay","title":"Fire-Lite PAM-4 10A Form C Relay","description":"\u003ch2\u003eFire-Lite PAM-4 9-40Vdc 10A Form C Relay\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003ePAM-4: Relay · Single SPDT · LED · 10A Form C Contacts · 9 to 40V DC\u003c\/p\u003e\n\u003cp\u003ePAM multi-voltage relay modules are ideal for applications where remote relays are required for control or status feedback.\u003c\/p\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-6755.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePAM-1, PAM-2, and PAM-4 Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-6755.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePAM-1, PAM-2, and PAM-4 Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-6755.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePAM-1- PAM-2- and PAM-4 Multi-Voltage Relay Modules Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52068.pdf\" target=\"_blank\" rel=\"noopener\"\u003ePAM-1 and PAM-2 Multi-Voltage Relay Modules Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Fire-Lite","offers":[{"title":"Default Title","offer_id":43133152493792,"sku":"PAM-4","price":18.2,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/fire-lite-relays-default-title-fire-lite-pam-4-10a-form-c-relay-31896816746720.jpg?v=1763280402"},{"product_id":"potter-rly-5-relay-expander","title":"Potter RLY-5 Relay Expander Card, 5 Configurable Relays, P-Link RS-485","description":"\u003cp\u003e\u003cstrong\u003ePotter RLY-5\u003c\/strong\u003e — relay expander card adding five configurable relay outputs to a compatible Potter fire alarm control panel over the P-Link bus.\u003c\/p\u003e\u003cp\u003eThe card talks to the panel on the four-wire RS-485 P-Link bus, a connection that is both power limited and supervised, and its outputs are configured in the Potter Configuration Software rather than by jumper. Each relay brings out normally closed, common and normally open terminals. Relay power is taken separately, from the panel or any fire listed supply.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eFive configurable relays rated 3.0 A at 24 VDC and at 125 VAC resistive\u003c\/li\u003e\n\u003cli\u003eP-Link draw at 24 VDC of 25 mA standby and 35 mA in alarm\u003c\/li\u003e\n\u003cli\u003eRelay power input 16–33 VDC at 10 mA standby and 135 mA in alarm\u003c\/li\u003e\n\u003cli\u003eUp to 31 RLY-5 cards per panel, P-Link runs to 6,500 feet\u003c\/li\u003e\n\u003cli\u003eFor IPA Series, AFC\/ARC Series and PFC-4064 panels\u003c\/li\u003e\n\u003cli\u003eAlso the legacy P-Series and PFC-6000 Addressable Series\u003c\/li\u003e\n\u003cli\u003eUUKL listed for smoke control, CSFM 7305-0328:0200\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe stacker bracket it mounts on is included, but an enclosure is not: the card goes in an AE-2, AE-8 or AE-14 accessory enclosure, or inside a PSN-1000E supply or a larger panel enclosure.\u003c\/p\u003e","brand":"Potter","offers":[{"title":"Default Title","offer_id":43530501652704,"sku":"RLY-5","price":529.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/potter-relays-default-title-potter-rly-5-relay-expander-36739672047840.jpg?v=1763281277"},{"product_id":"potter-pad100-trti-two-relay-two-input-module","title":"Potter PAD100-TRTI Two Relay Two Input Module","description":"\u003ch2\u003eThe PAD100-TRTI uses one (1) SLC loop address when monitoring two (2) Class B circuits or one (1) Class A circuit\u003c\/h2\u003e\n\u003cp\u003eThe PAD100-TRTI also provides two (2) Form C relay contacts. The module mounts on either a 4\" square or double gang box. The module is capable of monitoring two (2) separate Class B circuits making it ideal for monitoring sprinkler waterflow and valve tamper switches when they are located in the same proximity.\u003c\/p\u003e\n\u003cp\u003eThe PAD100-TRTI includes one red LED to indicate the module's status. In normal condition, the LED flashes when the device is being polled by the control panel. When an input is activated, the LED will flash at a fast rate.\u003cbr\u003e\u003cbr\u003e\u003c\/p\u003e","brand":"Potter","offers":[{"title":"Default Title","offer_id":43566413447392,"sku":"PAD100-TRTI","price":231.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/potter-relays-default-title-potter-pad100-trti-two-relay-two-input-module-32101178278112.jpg?v=1763281289"},{"product_id":"potter-mr-801-t-spdt-relay-track-mount","title":"Potter MR-801\/T SPDT Relay Track Mount","description":"\u003cp\u003e\u003cstrong\u003ePotter MR-801\/T\u003c\/strong\u003e — single-position SPDT multi-voltage control relay supplied with snap-track mounting hardware.\u003c\/p\u003e\u003cp\u003eMR-800 Series relays give a fire alarm, HVAC or lighting panel local dry contacts able to switch a load at line voltage, with a red LED that lights when the coil is energized. The \/T suffix is the mounting style: the relay ships with a 3.5 in. wide low-profile snap track and screws for fitting inside a standard cabinet, and takes the optional TK-CL DIN rail clip.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eOne dry Form C (SPDT) contact, single position\u003c\/li\u003e\n\u003cli\u003eResistive 10 A at 120 VAC, 7 A at 30 VDC \/ 277 VAC; inductive 0.25 \/ 0.33 hp at 120 \/ 250 VAC\u003c\/li\u003e\n\u003cli\u003eCoil 24 VDC at 22 mA, 24 VAC at 60 mA or 120 VAC at 26 mA; DC input polarized\u003c\/li\u003e\n\u003cli\u003e3.50 × 2.00 × 1.375 in. H\/W\/D; 14 to 22 AWG terminals\u003c\/li\u003e\n\u003cli\u003eUL Recognized Component (UL 864, UOXX2, file S3403), not UL Listed\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe suffix is the whole difference. MR-801\/C and MR-801\/C\/R are the same relay in a grey or red enclosure and carry the UL Listing; MR-801\/S ships with spacers; MR-804\/T and MR-808\/T have four and eight positions. Potter MR-101\/T is a different SPDT relay, MR-201\/T its DPDT counterpart.\u003c\/p\u003e","brand":"Potter","offers":[{"title":"Default Title","offer_id":43601832870112,"sku":"MR-801\/T","price":15.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/potter-relays-default-title-potter-mr-801-t-spdt-relay-track-mount-31896919081184.jpg?v=1763281310"},{"product_id":"edwards-mr-101-c-spdt-aux-relay","title":"Edwards MR-101\/C SPDT Auxiliary Relay with Cover","description":"\u003cp\u003e\u003cstrong\u003eEdwards MR-101\/C\u003c\/strong\u003e — single-position SPDT multi-voltage control relay with coil LED, factory mounted in a metal enclosure.\u003c\/p\u003e\u003cp\u003eThe MR-100\/200 series gives a fire alarm, HVAC, security or lighting-control system a set of dry Form C contacts that can be driven from any one of four input voltages by landing the coil wires on the matching input terminals. DC inputs are polarized. A red LED at the relay position lights when the coil is energized, so an installed relay can be checked without a meter. The \/C suffix means the relay is supplied in an enclosure rather than on snap track.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eSPDT, one Form C contact set, one module position\u003c\/li\u003e\n\u003cli\u003eContacts: 10 A @ 120 VAC (N.O. 1\/6 HP, N.C. 1\/8 HP), 7 A @ 28 VDC, 7 A @ 230 VAC\u003c\/li\u003e\n\u003cli\u003eCoil: 18–35 VDC, 18–35 VAC, 120 VAC or 230 VAC; 18 mA per position\u003c\/li\u003e\n\u003cli\u003eEnclosure 5.125 × 3.125 × 2.50 in.; 18 ga. backbox, 1\/2 in. knockouts, grey cover\u003c\/li\u003e\n\u003cli\u003e32°F to 120°F; terminals accept #14 to #22 AWG\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eOrder the suffix deliberately: MR-101\/T is the same SPDT relay on snap track with no enclosure, MR-101\/C\/R is the red-cover version, and MR-201\/C is the DPDT relay in the identical box.\u003c\/p\u003e","brand":"Edwards","offers":[{"title":"Default Title","offer_id":43766697427168,"sku":"MR-101\/C","price":36.85,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/edwards-relays-default-title-edwards-mr-101-c-spdt-aux-relay-31896764842208.jpg?v=1763282234"},{"product_id":"edwards-siga-crh-high-power-control-relay","title":"Edwards SIGA-CRH Signature High Power Control Relay Module, Two Form C Sets, 7 A at 120 VAC","description":"\u003cp\u003e\u003cstrong\u003eEdwards SIGA-CRH\u003c\/strong\u003e — addressable Signature Series control relay module for interfaces needing a high voltage, high current relay.\u003c\/p\u003e\u003cp\u003eOrdinary Signature control relays are pilot-duty parts; this one switches the load itself, so door closers, fans and dampers run straight off the loop. It carries one relay with two identical Form C contact sets that transfer together, and the output terminals are not supervised.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003e7 A at 120 V and at 240 V 50\/60 Hz (PF 0.75); 3.0 A at 120 V and 1.5 A at 240 V (PF 0.35); 6 A resistive at 24 VDC; audio switching 0 to 20 kHz\u003c\/li\u003e\n\u003cli\u003eSLC 15.20 to 19.95 VDC, 75 µA maximum standby and activated; one electronically assigned address\u003c\/li\u003e\n\u003cli\u003ePersonality Code 8, dry contact output; up to 60 per signaling line circuit\u003c\/li\u003e\n\u003cli\u003eDouble-gang or 4 in. square box, 2-1\/8 in. deep; UL 864 and CAN\/ULC-S527; EST3, EST3X and iO Series\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe plain SIGA-CR shares Personality Code 8 and the same 75 µA draw but is rated only 2 A at 24 VDC pilot duty and 0.5 A at 120 VAC. SIGA-MCR is that relay on a UIO motherboard and SIGA-CRR reverses polarity.\u003c\/p\u003e","brand":"Edwards","offers":[{"title":"Default Title","offer_id":43766699229408,"sku":"SIGA-CRH","price":145.55,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/edwards-relays-default-title-edwards-siga-crh-high-power-control-relay-31896767332576.jpg?v=1763282314"},{"product_id":"simplex-2098-9737-det-acc-relay-dpdt-3a","title":"Simplex 2098-9737 Supervised Relay, DPDT, Remote or Base Mount","description":"\u003cp\u003e\u003cstrong\u003eSimplex 2098-9737\u003c\/strong\u003e — supervised auxiliary relay with DPDT contacts for Simplex detector and sensor bases.\u003c\/p\u003e\u003cp\u003eThis relay gives one detector location a set of dry contacts for door holders, damper and fan shutdown or elevator interface. It is driven from the base and its connection is supervised, so a fault is annunciated at the panel. It mounts remotely or in the base electrical box, and Simplex documents it both with the addressable TrueAlarm 4098-9791 sensor base and with the older conventional 2098-9536 four-wire detector base.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eContacts: DPDT, two Form C, resistive or suppressed loads\u003c\/li\u003e\n\u003cli\u003ePower limited rating: 3 A at 28 VDC\u003c\/li\u003e\n\u003cli\u003eNon-power-limited rating: 3 A at 120 VAC\u003c\/li\u003e\n\u003cli\u003eCoil: externally supplied 18 to 32 VDC, nominal 24 VDC\u003c\/li\u003e\n\u003cli\u003eWith the 4098-9791 base: 270 µA supervisory, 28 mA in alarm\u003c\/li\u003e\n\u003cli\u003eRelay size: 2 1\/2 × 1 1\/2 × 1 in.\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eConfirm the base first. The 4098-9780 two-wire base takes the 4098-9860 relay instead, which is SPDT and rated 2 A at 30 VDC, and the 4098-9822 is an unsupervised relay that only tracks the base LED.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43777810399456,"sku":"2098-9737","price":75.3,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-fire-alarms-default-title-simplex-2098-9737-det-acc-relay-dpdt-3a-31897021022432.jpg?v=1763282488"},{"product_id":"simplex-4098-9843","title":"Simplex 4098-9843 Relay Form C SPDT PAM-SD","description":"\u003cp\u003e\u003cstrong\u003eSimplex 4098-9843\u003c\/strong\u003e — epoxy-encapsulated SPDT control relay (PAM-SD), 24 VDC coil.\u003c\/p\u003e\u003cp\u003eThis is the part that lets a fire alarm panel operate something that is not a fire alarm device: HVAC shutdown, door release, elevator capture, damper control, or any other auxiliary function that needs a clean dry contact. The relay is fully encapsulated in epoxy, which is why it can live in a mechanical room or inside an air handler enclosure where an open relay would not survive.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eForm C (SPDT) contacts\u003c\/li\u003e\n\u003cli\u003eCoil input 18–32 VDC; 15 mA at 24 VDC\u003c\/li\u003e\n\u003cli\u003eContact rating 7 A at 0.35 p.f. at 28 VDC and 120 VAC; 250 µA at 5 VDC\u003c\/li\u003e\n\u003cli\u003eColour-coded 18 AWG (0.82 mm²) wire leads; no LED\u003c\/li\u003e\n\u003cli\u003eRated for 100% RH condensing humidity\u003c\/li\u003e\n\u003cli\u003eUL 864 listed as Control Unit Accessory (UOXX); CSFM approved\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eEncapsulated construction means it is not field-repairable — it is replaced as a unit, which is normally cheaper than the labour of diagnosing an open relay in a dirty environment.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":43777820229856,"sku":"4098-9843","price":38.75,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-fire-alarms-default-title-simplex-4098-9843-31897057624288.jpg?v=1771337144"},{"product_id":"fire-lite-mr-104-cr-relay","title":"Fire-Lite MR-104\/CR Relay, Enclsr, Metal, 4 SPDT, Red","description":"\u003ch2\u003eFire-Lite MR-104\/CR Relay, Enclsr, Metal, 4 SPDT, Red\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-3477.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMR Series Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-51131.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMR Series Control Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/CS-2481.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMR-PAM Multi-Voltage Control Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/ds-1040.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-voltage Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Fire-Lite","offers":[{"title":"Default Title","offer_id":43790993293536,"sku":"MR-104\/CR","price":125.35,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/fire-lite-relays-default-title-fire-lite-mr-104-cr-relay-31896815337696.jpg?v=1763283440"},{"product_id":"fire-lite-r-14t-4-gang-relay-spdt-multivolt","title":"Fire-Lite R-14T 4-Gang Relay, SPDT, Multivolt","description":"\u003ch2\u003eFire-Lite R-14T 4-Gang Relay, SPDT, Multivolt, Track Mount\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-14T: Multi-Voltage Relay · 4-Gang 1 Form C (SPDT) Relay with 4 Red LEDs · Track Mount\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/moved-ss\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T-R-20T-R-14T-R-24T Multi Voltage Relay\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T, R-20T, R-14T, R-24T Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Fire-Lite","offers":[{"title":"Default Title","offer_id":43847538344160,"sku":"R-14T","price":50.9,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/fire-lite-relays-default-title-fire-lite-r-14t-4-gang-relay-spdt-multivolt-32309101068512.jpg?v=1763283574"},{"product_id":"gamewell-fci-gwrce-95-relay-control-element","title":"Gamewell-FCI GWRCE-95 (RCE-95) Relay Control Element","description":"\u003cp\u003e\u003cstrong\u003eGamewell-FCI RCE-95\u003c\/strong\u003e — addressable relay control element that interfaces panel analog circuits to building functions and reports whether they actually operated.\u003c\/p\u003e\u003cp\u003eFire alarm panels must drive equipment they do not own: door holders, elevator recall, dampers, motors. The RCE-95 supplies the dry contacts from the signalling line circuit, plus a feedback input so the panel learns the equipment status instead of assuming the command took effect.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eFor Gamewell-FCI 600 Series and ILI95-E3 Series analog addressable panels; XP95\u003c\/li\u003e\n\u003cli\u003eTwo-wire non-polarized SLC connection; Style 4, 6 or 7 wiring; fully supervised\u003c\/li\u003e\n\u003cli\u003eForm-C dry contacts rated 2.0 A at 30 VDC or 0.2 A at 120 VAC, behind a 2 amp Slo Blow fuse\u003c\/li\u003e\n\u003cli\u003e24 VDC from the analog circuit; standby current 0.0008 A, alarm current 0.0015 A\u003c\/li\u003e\n\u003cli\u003eIntegral LED annunciates activation; address set by a single DIP switch on the board\u003c\/li\u003e\n\u003cli\u003eSurface or flush mount in a standard 4.688 in. backbox; 32 to 120 °F\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eTrim ring 70839 is ordered separately for flush mounting. RCD is the optional Relay Control Display, one per eight elements, and it works only with the IdentiFlex 632 and IF650.\u003c\/p\u003e","brand":"Gamewell-FCI","offers":[{"title":"Default Title","offer_id":44322208284896,"sku":"GWRCE-95","price":250.45,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/gamewell-fci-relays-default-title-gamewell-fci-gwrce-95-relay-control-element-31982830944480.jpg?v=1763284518"},{"product_id":"simplex-4100-3209","title":"Simplex 4100-3209 Eight-Point SPDT Relay Module, 3 A, 4100ES Expansion Bay","description":"\u003cp\u003e\u003cstrong\u003eSimplex 4100-3209\u003c\/strong\u003e — eight single-pole double-throw relay module for 4100ES fire alarm control panels.\u003c\/p\u003e\u003cp\u003eThe card gives a 4100ES eight independent Form C dry contacts the site program can drive for ancillary control such as door release, damper and fan interlock or third-party signalling. It is non power-limited, so Simplex restricts it to the expansion bay rather than the master controller bay.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eEight single-pole, double-throw (SPDT) switches on one card\u003c\/li\u003e\n\u003cli\u003eResistive rating 3 A at 30 VDC or 120 VAC\u003c\/li\u003e\n\u003cli\u003eInductive rating 1.5 A at 30 VDC or 120 VAC\u003c\/li\u003e\n\u003cli\u003eOne block of chassis space, a block being a 4 × 5 in. card area\u003c\/li\u003e\n\u003cli\u003eDraws 16 mA supervisory and 200 mA in alarm\u003c\/li\u003e\n\u003cli\u003eNon power-limited; expansion bay mounting only\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe 3 A figure is the resistive rating and an inductive load such as a contactor coil is held to half of it. Nearby cards differ: 4100-3207 and 4100-3208 are four DPDT switches with contact feedback at 2 A and 10 A, and 4100-6033 is the three-relay alarm, trouble and supervisory module.\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":44955386970336,"sku":"4100-3209","price":187.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/products\/simplex-fire-alarms-default-title-simplex-4100-3209-32541225976032.webp?v=1763284850"},{"product_id":"notifier-011145f-bi-directional-paging","title":"Notifier 011145F Bi-Directional Paging","description":"\u003ch2\u003eNotifier 011145F Bi-Directional Paging Relay\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-62030.pdf\" target=\"_blank\" rel=\"noopener\"\u003eUNP-Unified Notification Platform- Paging Relay Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-62029.pdf\" target=\"_blank\" rel=\"noopener\"\u003eUNP-Unified Notification Platform- Mass Notification Ecosystem Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/notices-and-notifications\/product-bulletins\/notifier-us\/hon-ba-fire-notifier-unp-product-announcement-12-04-2019.pdf\" target=\"_blank\" rel=\"noopener\"\u003eUNP -Unified Notification Platform- Product Bulletin\u003c\/a\u003e (Product Bulletin)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Notifier","offers":[{"title":"Default Title","offer_id":46115310731488,"sku":"011145F","price":2353.15,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/notifier-relays-default-title-notifier-011145f-bi-directional-paging-34291111657696.jpg?v=1763285012"},{"product_id":"system-sensor-r-10e-multi-voltage-conventional-relay","title":"System Sensor R-10E Multi-Voltage Conventional Relay","description":"\u003ch2\u003eSystem Sensor R-10E Multi-Voltage Conventional Relay, Single (SPDT) Relay with Activation LED\u003cbr\u003e\n\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-10E: Multi-Voltage Relay, 1 Form C (SPDT) Relay, Red LED, Steel Enclosure, UL Listed\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage-Relay_Manual_I56-2536.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10E, R-20E, R-14E, R-24E Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":46202445037792,"sku":"R-10E","price":44.45,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/system-sensor-relays-default-title-system-sensor-r-10e-multi-voltage-conventional-relay-34518792077536.jpg?v=1763285047"},{"product_id":"system-sensor-r-14e-multi-voltage-conventional-relay","title":"System Sensor R-14E Multi-Voltage Conventional Relay","description":"\u003ch2\u003eSystem Sensor R-14E Multi-Voltage Conventional Relay, 4-Gang (SPDT) Relay with Activation LEDs\u003cbr\u003e\n\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-14E: Multi-Voltage Relay, 4-Gang 1 Form C (SPDT) Relay with 4 Red LEDs, Steel Enclosure\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage-Relay_Manual_I56-2536.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10E, R-20E, R-14E, R-24E Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":46202445693152,"sku":"R-14E","price":108.2,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/system-sensor-fire-alarms-default-title-system-sensor-r-14e-multi-voltage-conventional-relay-34518792175840.jpg?v=1763285021"},{"product_id":"system-sensor-r-20t","title":"System Sensor R-20T Single 1 Form C (SPDT) Relay","description":"\u003ch2\u003eSystem Sensor R-20T Single 1 Form C (SPDT) Relay with a red LED\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-20T: Multi-Voltage Relay, Single 2 Form C (DPDT) Relay, Red LED, Track Mount, UL Listed\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/installation-guides\/moved-ss\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T-R-20T-R-14T-R-24T Multi Voltage Relay\u003c\/a\u003e (Installation Manual)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage_Relay_Manual_I56-2533.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10T, R-20T, R-14T, R-24T Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":46202446414048,"sku":"R-20T","price":31.3,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/system-sensor-fire-alarms-default-title-system-sensor-r-20t-34518792012000.jpg?v=1763285057"},{"product_id":"functional-devices-ribu1c-enclosed-relay","title":"Functional Devices RIBU1C Enclosed Pilot Relay, 10 Amp SPDT, 10-30 Vac\/dc and 120 Vac Coil","description":"\u003cp\u003e\u003cstrong\u003eFunctional Devices RIBU1C\u003c\/strong\u003e — enclosed 10 amp SPDT pilot control relay with a dual 10–30 Vac\/dc and 120 Vac coil in a NEMA 1 housing.\u003c\/p\u003e\u003cp\u003eRIB packaging puts relay, socket, transient protection, status LED and housing in one prewired assembly, so a low-voltage controller output can switch a line-voltage load.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eOne SPDT continuous-duty relay, 10 amp resistive at 277 Vac and at 28 Vdc\u003c\/li\u003e\n\u003cli\u003eCoil 10–30 Vac\/dc or 120 Vac, 50–60 Hz; pull-in 9 Vac \/ 10 Vdc, drop-out 2.1 Vac \/ 2.8 Vdc\u003c\/li\u003e\n\u003cli\u003eCoil current 46 mA at 24 Vac, 18 mA at 24 Vdc, 28 mA at 120 Vac\u003c\/li\u003e\n\u003cli\u003e480 VA pilot duty at 240–277 Vac; 600 W tungsten at 120 Vac normally open, 240 W normally closed\u003c\/li\u003e\n\u003cli\u003eOperate time 20 ms, 10 million cycles minimum mechanical life, gold-flash contacts\u003c\/li\u003e\n\u003cli\u003e1.70\" H × 2.80\" W × 1.50\" D, 0.50\" NPT nipple, 16\" 600 V leads\u003c\/li\u003e\n\u003cli\u003eUL916 listed, accepted for use in plenum; -30 to 140 °F\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eFunctional Devices lists UL864 and California State Fire Marshal against the red RIBU1C-RD, not this model, so specify the RIBU1C-RD where a fire signalling listing is required. RIBH1C is the same relay with a 208–277 Vac coil; RIBU1C-N4 uses a NEMA 4X enclosure under UL508.\u003c\/p\u003e","brand":"Functional Devices","offers":[{"title":"Default Title","offer_id":46206052040928,"sku":"RIBU1C","price":29.45,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/functional-devices-fire-alarms-default-title-functional-devices-ribu1c-enclosed-relay-34518800695520.jpg?v=1763285177"},{"product_id":"space-age-ssu-pam-4-pam-series-multi-voltage-encapsulated-relay","title":"Space Age SSU-PAM-4 PAM-Series Multi-Voltage Encapsulated Relay","description":"\u003ch2\u003eSpace Age SSU-PAM-4 PAM-Series Multi-Voltage Encapsulated Relay, 10A, 12-40VDC, SPDT\u003c\/h2\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":46206110990560,"sku":"SSU-PAM-4","price":18.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/space-age-relays-default-title-space-age-ssu-pam-4-pam-series-multi-voltage-encapsulated-relay-34766029750496.jpg?v=1763285160"},{"product_id":"space-age-ssu-mr-101-c-1-spdt-10-amp-relay","title":"Space Age SSU-MR-101\/C 1 SPDT 10 Amp Relay","description":"\u003ch2\u003eSpace Age SSU-MR-101\/C 1 SPDT 10 Amp Relay, LED, Grey Encl., 24VAC\/DC, 115VAC, 230VAC\u003c\/h2\u003e","brand":"Space Age","offers":[{"title":"Default Title","offer_id":46737182130400,"sku":"SSU-MR-101\/C","price":28.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/space-age-relays-default-title-space-age-ssu-mr-101-c-1-spdt-10-amp-relay-35928643109088.jpg?v=1763285599"},{"product_id":"napco-rb1000-c-form-relay-board-12v","title":"Napco RB1000 C-Form Relay Board, 12V","description":"\u003ch2\u003eNapco RB1000 Low-Current Form-C relay that will provide an additional dry contact output when connected to an “E” output lug on a Napco control panel\u003cbr\u003e\u003cbr\u003e\n\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eThe RB1000 is a relay board accessory for Napco control panels. Napco lists it (\"RB1000: relay board\") among the ordering accessories for Gemini hybrid panels such as the GEM-P9600 and GEM-P3200, where it is used to provide an extra relay output.\u003c\/p\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/napcosecurity.com\/media\/pdfs\/a400b_p9600specw.pdf\" target=\"_blank\" rel=\"noopener\"\u003eGemini GEM-P9600 Spec Sheet (A400B) - accessory list\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/napcosecurity.com\/media\/pdfs\/a401b_p3200specw.pdf\" target=\"_blank\" rel=\"noopener\"\u003eGemini GEM-P3200 Spec Sheet (A401B) - accessory list\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Napco","offers":[{"title":"Default Title","offer_id":46826176708832,"sku":"RB1000","price":21.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/napco-relays-default-title-napco-rb1000-c-form-relay-board-12v-36298474160352.jpg?v=1763285686"},{"product_id":"simplex-2088-9007-mr101-relay","title":"Simplex 2088-9007 One-Position SPDT Relay","description":"\u003ch2\u003eSimplex 2088-9007 MR101 Relay, SPDT W\/ LED \u003cspan\u003eTrack mount without cover\u003c\/span\u003e\n\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eSingle relay module or four relay module, with or without cover, with SPDT or DPDT contacts\u003c\/li\u003e\n\u003cli\u003eLED indicates relay module status\u003c\/li\u003e\n\u003cli\u003eCover provide status LED viewing ports\u003c\/li\u003e\n\u003cli\u003eMultiple coil voltage inputs, diode polarized for DC\u003c\/li\u003e\n\u003cli\u003eModules are track mounted with snap-apart feature design allowing the four relay module to be separated\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\u003cli\u003e\n\u003ca href=\"https:\/\/docs.johnsoncontrols.com\/simplex\/api\/khub\/documents\/ZOwiUG74OprG5yAbIgFniA\/content\" target=\"_blank\" rel=\"noopener\"\u003eFire Alarm Control Relays, Track Mount and Encapsulated; Model 4098-9843 and 2088 Series\u003c\/a\u003e (Datasheet)\u003c\/li\u003e\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":46826243326176,"sku":"2088-9007","price":45.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/2088-9007_1b24e663-43d7-4d0b-b2bd-e2b5aa4b7876.jpg?v=1781871381"},{"product_id":"hubbell-omnidt2000rp-pir-ultrasonic-low-voltage-ceiling-sensor","title":"Hubbell OMNIDT2000RP OMNI Dual Technology Ceiling Occupancy Sensor, 2000 sq ft, Relay and Photocell","description":"\u003cp\u003e\u003cstrong\u003eHubbell Control Solutions OMNIDT2000RP\u003c\/strong\u003e — an OMNI dual-technology ceiling occupancy sensor rated for 2,000 square feet, with the -RP relay and photocell option.\u003c\/p\u003e\u003cp\u003eIt uses ultrasonic and passive infrared sensing together to switch lighting on occupancy, under IntelliDAPT firmware that adjusts sensitivity and timing by itself. It is a sensor head, not a switch: Hubbell states it needs a UVPP or MP-Series power pack, sold separately.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003eThe ordering block decodes it: OMNI, DT dual technology, 2000 for coverage, RP for relay and photocell\u003c\/li\u003e\n\u003cli\u003eTriggering is a switch setting — A2 off demands both infrared AND ultrasonic, A2 on accepts either alone\u003c\/li\u003e\n\u003cli\u003eRelay: SPDT with NO and NC contacts, 500 mA at 24 VDC, three-wire isolated\u003c\/li\u003e\n\u003cli\u003ePhotocell: adjustable daylight override, 0 to 100 foot-candles\u003c\/li\u003e\n\u003cli\u003eUltrasonic 32 kHz; infrared by dual-element pyrometer and Fresnel lens\u003c\/li\u003e\n\u003cli\u003e24 VDC at 33 mA; timer 8 to 30 minutes automatic, 8 seconds in test\u003c\/li\u003e\n\u003cli\u003e4.5 in. diameter by 1.5 in. high, indoor only, UL and cUL listed\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eThe number is the specification: OMNIDT1000 and OMNIDT500 are the smaller coverages, and a plain OMNIDT2000 has neither option.\u003c\/p\u003e","brand":"Hubbell Control Solutions","offers":[{"title":"Default Title","offer_id":46826539057376,"sku":"OMNIDT2000RP","price":245.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/hubbell-control-solutions-montion-sensors-default-title-hubbell-omnidt2000rp-pir-ultrasonic-low-voltage-ceiling-sensor-37690982301920.jpg?v=1763285802"},{"product_id":"simplex-4100-3003","title":"Simplex 4100-3003 8 PT AUX Relay MOD 3 AMP","description":"\u003cp\u003e8 PT AUX RELAY MOD 3 AMP\u003c\/p\u003e","brand":"Simplex","offers":[{"title":"Default Title","offer_id":46826595320032,"sku":"4100-3003","price":361.3,"currency_code":"USD","in_stock":false}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/simplex-fire-alarms-default-title-simplex-4100-3003-36033500479712.webp?v=1763285775"},{"product_id":"system-sensor-r-20e-multi-voltage-single-2-form-c","title":"System Sensor R-20E Multi Voltage Single 2 Form C","description":"\u003ch2\u003eSystem Sensor R-20E Multi Voltage Single 2 Form C (DPDT) Relay with Red LED\u003cbr\u003e\n\u003c\/h2\u003e\u003cdiv class=\"ths-mfr-data\"\u003e\n\u003cp\u003eR-20E: Multi-Voltage Relay, Single 2 Form C (DPDT) Relay, Red LED, Steel Enclosure, UL Listed\u003c\/p\u003e\n\u003cp\u003eMulti-voltage conventional relays are used for high-current switching applications such as fans and damper assembly controls, door controls, air handling unit controls, and other types of system interfacing.\u003c\/p\u003e\n\u003ch3\u003eKey Features\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eMulti-voltage operation\u003c\/li\u003e\n\u003cli\u003eActivation LEDs\u003c\/li\u003e\n\u003cli\u003eEasy and flexible installation\u003c\/li\u003e\n\u003cli\u003eExpanded color options\u003c\/li\u003e\n\u003cli\u003eReliable and robust design\u003c\/li\u003e\n\u003cli\u003eMultipurpose field installations\u003c\/li\u003e\n\u003cli\u003eMulti-voltage relays with terminal strip field wiring connections, mounting track, and hardware for R-10T\/20T and R-14T\/24T\u003c\/li\u003e\n\u003cli\u003eRemovable front cover on steel enclosure for R-10E\/R-20E and R-14\/R-24E, which mount inside the enclosure\u003c\/li\u003e\n\u003cli\u003eLED viewing hole on top of the steel enclosure’s cover\u003c\/li\u003e\n\u003cli\u003eExtra pair of wires for redundant power input on PR-3 and PR-3A\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003eDocuments \u0026amp; Downloads\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/df-52404.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hbt-fire-DN-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/MultiVoltage_Relays_DataSheet_A05-0372.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Relays Datasheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/literature-and-specs\/datasheets\/notifier-us\/hon-ba-fire-dn-7015.pdf\" target=\"_blank\" rel=\"noopener\"\u003eMulti-Voltage Conventional Relays Data Sheet\u003c\/a\u003e (Data Sheet)\u003c\/li\u003e\n\u003cli\u003e\n\u003ca href=\"https:\/\/prod-edam.honeywell.com\/content\/dam\/honeywell-edam\/hbt\/en-us\/documents\/manuals-and-guides\/user-manuals\/MultiVoltage-Relay_Manual_I56-2536.pdf\" target=\"_blank\" rel=\"noopener\"\u003eR-10E, R-20E, R-14E, R-24E Multi Voltage Relay Manual\u003c\/a\u003e (User Manual)\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/div\u003e","brand":"System Sensor","offers":[{"title":"Default Title","offer_id":47373182075104,"sku":"R-20E","price":50.45,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0653\/7186\/5312\/files\/system-sensor-fire-alarms-default-title-system-sensor-r-20e-multi-voltage-single-2-form-c-37387936661728.jpg?v=1763286257"}],"url":"https:\/\/thefirealarmsupplier.com\/collections\/relays.oembed?page=4","provider":"The Fire Alarm Supplier","version":"1.0","type":"link"}